TABLE P2902.7.1
DISTANCE FROM SOURCES OF CONTAMINATION TO PRIVATE WATER SUPPLIES AND PUMP SUCTION LINES | |
Source of Contamination | Distance (feet) (1 foot=304.8mm) |
Sewer | 50 |
Septic Tank | 50 |
Pasture | 100 |
Sewer (leaded or mechanical joints or approved plastic) | 10 |
Subsurface pits | 100c |
Seepage pits | 100 |
Cesspools | 100 |
Barnyard | 100 |
Farm silo | 25 |
Pump house floor drain of cast iron draining to ground surface | 2 |
Minimum static pressure shall be forty (40) psi measured before any meter, or a booster pump shall be installed after the meter providing forty (40) psi minimum static pressure.
For private wells, forty (40) psi minimum shall be provided at the outlet of any storage tank or pump.
Delete section P2904 and substitute the following:
Automatic fire sprinkler if installed at the applicant's option will be in conformance with Appendix RP.
510 R.I. Code R. 510-RICR-00-00-2.23
Amended effective 2/1/2022