510 R.I. Code R. 510-RICR-00-00-2.22

Current through December 3, 2024
Section 510-RICR-00-00-2.22 - Chapter 26
P2603.4 Add the following exception to section P2603.4 Pipes through footings or foundation walls:

Exception:

PVC schedule forty (40) minimum pipe shall not be required to be sleeved or be provided with a relieving arch.

P2603.5 Add the following exception to section P2603.5 Freezing:

Exception:

Soil and vent stacks located within exterior walls and vent pipes in attics shall not be required to be insulated.

P2603.5.1 Delete section P2603.5.1 and substitute the following
P2603.5.1 Sewer Depth.

Building sewers that connect to private sewage disposal systems shall meet the requirements of the Department of Environmental Management's Regulations for onsite wastewater treatment systems, 250-RICR-150-05-4 and 250-RICR-150-10 Parts 1 through 8.

Building sewers connecting to a public sewer shall be a minimum of thirty-six inches (36") below grade.

510 R.I. Code R. 510-RICR-00-00-2.22

Amended effective8/1/2019
Amended effective 2/1/2022