La. Admin. Code tit. 51 § XIV-721

Current through Register Vol. 50, No. 11, November 20, 2024
Section XIV-721 - Cleanout Clearances
A. Small Pipe. Cleanouts smaller than 3-inches shall be so installed that there is a clearance of not less than 12 inches (305 mm) for the purpose of rodding.
B. Large Pipe. Cleanouts on 3-inch or larger pipes shall be so located that there is a clearance of not less than 18 inches (457 mm) for the purpose of rodding.

La. Admin. Code tit. 51, § XIV-721

Promulgated by the Department of Health and Hospitals, Office of Public Health, LR 38:2852 (November 2012).
AUTHORITY NOTE: Promulgated in accordance with R.S. 40:4(A)(7) and R.S. 40:5(2)(3)(7)(9)(16)(17)(20).