La. Admin. Code tit. 51 § XIV-719

Current through Register Vol. 50, No. 11, November 20, 2024
Section XIV-719 - Size of Cleanouts
A. Pipes Less Than 8-inch Nominal Size. For pipes less than 8-inch nominal size, cleanouts shall be the same nominal size as the pipe to which they are connected.
1. Exceptions
a. Pipes larger than 4-inch nominal size may be served by a 4-inch cleanout;
b. A 1 1/4-inch "P" trap connected with slip joints or ground joint connections may be used to serve 1 1/2- inch pipe; and,
c. A 1 1/2-inch "P" trap connected with slip joints or ground joint connections may be used to serve a 2-inch pipe.
B. Pipes 8 Inches and Larger Nominal Size. For pipes 8 inches and larger nominal size, cleanouts shall comply with the following.
1. Building drains may be served with a 4-inch cleanout.
2. For building sewers 8 inches and larger, manholes shall be provided and located at each change in direction and at intervals of not more than 400 ft (121.9 m). Manholes and manhole covers shall conform to §717. G of this code.
3. Building drains 8-inch nominal size and larger shall have cleanouts located at intervals of not more than 100 ft (30.5 m) and at each change of direction over 45° (0.785 rad).

La. Admin. Code tit. 51, § XIV-719

Promulgated by the Department of Health and Hospitals, Office of Public Health, LR 38:2851 (November 2012).