D.C. Mun. Regs. tit. 12, 12-I405

Current through Register Vol. 71, No. 49, December 6, 2024
Section 12-I405 - ADDITIONAL EFFICIENCY PACKAGE
R405.1Requirements.

New buildings shall comply with at least one of the following:

1. Enhanced HVAC performance in accordance with Section R405.2.
2. Enhanced Building Envelope in accordance with Section R405.3.
3. Enhanced Air Leakage and Heat Recovery Ventilation in accordance with Section R405.4.
4. Enhanced Water Heating System in accordance with Section R405.5.

Exception:Alterations are exempt from Section R405.

TABLE R405.2

Equipment Type

Efficiency

Split and Packaged Air Conditioners

= 15 SEER a

Split and Packaged Air Source Heat Pumps

= 15 SEER a, = 9.0 HSPFb

Gas-fired Furnace

= 90% AFUEc and Furnace Fan Efficiency = 2.0% or Electronically Commutated Motor (ECM)

Gas-fired Boiler

= 90% AFUEc

Ground Source Heat Pump

= 17.1 EERd and = 3.6 COPe

a. SEER - Seasonal Energy Efficiency Ratio
b. HSPF - Heating Seasonal Performance Factor
c. AFUE - Annual Fuel Utilization Efficiency
d. EER - Energy Efficiency Ratio
e. COP - Coefficient of Performance
R405.3Enhanced Building Thermal Envelope.

Building Thermal Envelope shall comply with Table R405.3 in addition to Table R402.1.2.

TABLE R405.3 INSULATION AND FENESTRATION REQUIREMENTS BY COMPONENT

FENESTRATION

Windows = 0.24 U-Factor ENERGY STAR Compliant Doors

SKYLIGHT U-FACTOR

0.45 U-Factor

GLAZED FENESTRATION SHGC

0.40 Solar Heat Gain Coefficient (SHGC)

CEILING

R60

MASS WALL

U-factor less than or equal to .035 or R-19 cavity + R-10 continuous, or R-13 in cavity + R-15 continuous, or R-25 continuous

WOOD FRAME

U-factor less than or equal to .035 or R-19 cavity + R-10 continuous, or R-13 in cavity + R-15 continuous, or R-25 continuous

METAL FRAME WALL

U-factor less than or equal to .035

CONTINUOUS SLAB INSULATION

R10 continuous

R405.4Enhanced Air Leakage and Heat Recovery Ventilation.

Buildings shall meet the minimum air leakage requirements of Table R405.4 and install a heat or energy recovery ventilation system.

TABLE R405.4 AIR LEAKAGE TESTING REQUIREMENTS

New construction

Single family detached, two family attached (duplex), townhouses, flats

2 ACH50

Dwelling units in Multifamily buildings 3 stories and less

.25 CFM50/SF enclosure area of each unit or 2 ACH50

R405.5Efficient Appliances and Water Heating.

All refrigerators, freezers, dishwashers, clothes washers, and ceiling fans must be ENERGY STAR Qualified, and water heater(s) shall meet the minimum efficiency requirements of Table R405.5.

TABLE R405.5 MINIMUM EFFICIENCY FOR WATER HEATERS

Equipment Type

Efficiency

Gas Storage Water Heaters

>= 0.90 Energy Factor (EF)

Tankless Water Heaters

>= 0.95 Energy Factor (EF) with electronic ignition

Electric Water Heaters

>= 2.2 Energy Factor (EF)

D.C. Mun. Regs. tit. 12, 12-I405

Final Rulemaking published at 67 DCR 5679 (5/29/2020); amended by Final Rulemaking published at 68 DCR 007412 (7/30/2021)