Strike Section R406.2 (including Table R406.2) of the International Energy Conservation Code in their entirety and insert new Section R406.2 and Table R406.2 in the Energy Conservation Code-Residential Provisions in their place to read as follows.
Compliance with this section requires that the provisions identified in Sections R401 through R404 labeled as "mandatory" be met. The building thermal envelope shall be greater than or equal to Table R406.2.
TABLE R406.2 INSULATION AND FENESTRATION REQUIREMENTS BY COMPONENTa
FENESTRATION U-FACTORb | 0.35 U-Factor |
SKYLIGHTbU-FACTOR | 0.60 U-Factor |
GLAZED FENESTRATION SHGCb | No Requirement |
CEILING | R-38 |
WOOD FRAME WALL | R-13 |
MASS WALL | R-5 exterior continuous or R-10 interior continuous |
FRAME FLOOR | R-19 |
MASS FLOOR | R-15 |
BASEMENT WALL | R-10 continuous or R-13 in cavity |
SLAB c R-VALUE & DEPTH | R-10 for the first 2 feet |
CONDITIONED CRAWLSPACE WALL | R-10 continuous or R-13 in cavity |
For SI: 1 foot = 304.8 mm.
Strike Section R406.4 (including Table R406.4) of the International Energy Conservation Code in their entirety and insert new Section R406.4 and Table 406.4 in the Energy Conservation Code-Residential Provisions in their place to read as follows.
Compliance based on an ERI analysis requires that the rated design be shown to have an ERI less than or equal to 54 when compared to the ERI reference design .
Renewable energy. The use of renewable energy is not allowed to meet the minimum requirement of 54 as listed in R406.4.
D.C. Mun. Regs. tit. 12, 12-I406