023-3 Wyo. Code R. § 3-17

Current through April 27, 2019
Section 3-17 - Meter Accuracy, Measurement and Standards

(a) Inaccurate, improper or non-certified meters, including those for which accuracy has not been established, shall not be placed in service or allowed to remain in service. Meters that register upon zero load are considered inaccurate. New meters and serviced meters shall be in good repair and adjusted as closely as practicable to zero error. All meters shall conform to ANSI, IEC, AWWA and ISO, as applicable.

(b) All service meters shall clearly indicate the units of measurement for which the customer is charged. If the utility invoices customers in a different unit of measurement than the service meter indicates, the conversion factor shall be stated on the customer bill. Metering in the following units is required:

  • (i) Electric: kWh, kW or kVar depending upon service requirements;
  • (ii) Gas: cubic feet, dekatherms or therms;
  • (iii) Water: cubic feet or U.S. gallons.

023-3 Wyo. Code R. § 3-17

Adopted, Eff. 3/21/2016.

Amended, Eff. 4/8/2019.