(a) Owners and/or operators of storage tank systems shall ensure that repairs will prevent releases due to structural failure or corrosion as long as the storage tank system is used to store regulated substances. The repairs shall meet the following requirements: - (i) Repairs to UST systems shall be properly conducted in accordance with one or more of the following industry standards or practices:
- (A) NFPA Standard 30, as referenced in Section 2;
- (B) API Recommended Practice 2200, as referenced in Section 2;
- (C) API Standard 1631, as referenced in Section 2;
- (D) NFPA Standard 326, as referenced in Section 2;
- (E) National Leak Prevention Association Standard 631, as referenced in Section 2;
- (F) STI Recommended Practice R972, as referenced in Section 2;
- (G) NACE International Standard Practice SP0285, as referenced in Section 2; or
- (H) Fiberglass Tank and Pipe Institute Recommended Practice T-95-02, as referenced in Section 2.
- (ii) Repairs to aboveground storage tank systems shall be properly conducted in accordance with one or more of the following industry standards or practices:
- (A) NFPA Standard 30, as referenced in Section 2;
- (B) API Standard 620, as referenced in Section 2;
- (C) API Standard 650, as referenced in Section 2;
- (D) API Standard 653, as referenced in Section 2; or
- (E) PEI RP200, as referenced in Section 2.
- (iii) Repairs to fiberglass-reinforced plastic USTs may be made by the manufacturer's authorized representatives or in accordance with a code of practice developed by a nationally recognized association or an independent testing laboratory.
- (iv) Metal pipe sections and fittings that have released regulated substances as a result of corrosion or other damage shall be replaced. Non-corrodible pipes and fittings may be repaired in accordance with the manufacturer's specifications.
- (v) Repairs to secondary containment areas of tanks and piping used for interstitial monitoring and to containment sumps used for interstitial monitoring of piping shall have the secondary containment tested for tightness according to the manufacturer's instructions or a code of practice developed by a nationally recognized association or independent testing laboratory within 30 days following the date of completion of the repair. All other repairs to storage tank systems shall be tightness tested in accordance with Sections 14(g) and 16(b) within 30 days following the date of the completion of the repair unless:
- (A) The repaired storage tank system is internally inspected in accordance with a code of practice listed in this Section; or
- (B) The repaired portion of any UST system is monitored monthly for releases in accordance with a method specified in Section 16(c) through (j); or
- (C) Another test method is used that is determined by the department, pursuant to Section 33, to be no less protective of human health and the environment than those listed above.
- (D) The following codes of practice may be used to comply with paragraph (a)(v) of this Section:
- (I) STI Recommended Practice R012, as referenced in Section 2; or
- (II) Fiberglass Tank and Pipe Institute Recommended Practice 2007-2, as referenced in Section 2.
- (III) PEI RP1200, as referenced in Section 2.
- (vi) Storage tank system owners and/or operators shall maintain records of each repair until the UST system is permanently closed or undergoes a change-in-service pursuant to Part G of this Chapter.
(b) All owners and/or operators of repaired UST systems shall ensure the modifications meet the performance standards for design and repair as set forth in Section 6.
(c) Costs associated with remediation of any release from a storage tank system during tank installation or repair work by a tank installer, tester, owner and/or operator, etc., are not eligible for the state's corrective action account funds.
(d) Any time steel connected piping is repaired or modified by replacing the pipe with a non-corrodible pipe, all of the connected piping on that run shall be replaced. Any time steel piping that is not cathodically protected is repaired or replaced, the entire run of pipe shall be replaced with a non-corrodible pipe.
(e) Whenever the integrity of the primary or secondary wall of a double-wall tank has been compromised, repairs shall be made immediately in accordance with the tank manufacturer's recommendations. If the tank cannot be repaired, it shall be permanently closed in accordance with Section 31.
(f) Within 30 days following any repair to spill or overfill prevention equipment, the repaired spill or overfill prevention equipment shall be tested or inspected, as appropriate, in accordance with Section 10(d) to ensure it is operating properly.
(g) Testing required under this Section shall be conducted by a licensed installer as defined in Section 45 or a licensed tester as defined in Section 48.