This section applies to containers of three thousand gallons capacity or less and pertinent equipment mounted on farm trucks or trailers used for the transportation of ammonia.
In addition to this section, you need to follow the Appurtenances requirements for all systems, WAC 296-826-50005.
or
EXEMPTION: | The following do not need to be fitted with excess flow valves: |
1. Safety relief valves; | |
2. Those with openings from the containers or through fittings that are attached directly onto the container where pressure gauge connections are made as long as the openings are not larger than a No. 54 drill size. |
EXEMPTION: | You are exempt from the requirement not to install the shut off valve between the safety relief valve and the container or systems in the following situations: |
1. A three-way valve installed under two safety relief valves, each with: | |
a. The required rate of discharge; and | |
b. Installed to allow either of the safety relief valves to be closed off but not at the same time. | |
2. Two separate relief valves are installed with individual shut off valves. | |
The two shut off valve stems must be mechanically interconnected to allow the full required flow of one safety relief valve at all times. | |
3. When a safety relief valve manifold that allows: | |
a. One valve of two or more to be closed off and | |
b. The remaining valve or valves will provide not less than the rate of discharge shown on the manifold nameplate. |
Table 12
Appurtenances for Systems Mounted on Farm Trucks or Trailers
If you have: | Then make sure they: |
Filling connections | Are fitted with one of the following: 1. A combination back-pressure check valve and excess flow valve. 2. One double or 2 single backpressure check valves. 3. A positive shut off valve used with either an: a. Internal back-pressure check valve; or b. Internal excess flow valve. |
A fully enclosed guard | Have properly vented safety relief valves. |
Fittings | Are protected from physical damage by a rigid guard designed: 1. To withstand static loading in any direction equal to twice the weight of the container and lading. 2. With a safety factor of 4 based on the maximum strength of the material used. |
Liquid withdrawal lines installed in the bottom of the container | Have connections, including the hose that are not lower than the lowest horizontal edge of the truck axle. |
Columnar-type gauges | 1. Are shielded against the direct rays of the sun. 2. Are equipped with all of the following: a. Shut off valves having metallic hand-wheels; b. Excess flow valves; c. Extra heavy glass that is adequately protected with a metal housing applied by the gauge manufacturer. |
Hydrostatic relief valves | Are installed between each pair of valves in the liquid ammonia piping or hose. |
Wash. Admin. Code § 296-826-50025
Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, 49.17.060. 06-10-067, § 296-826-50025, filed 5/2/06, effective 9/1/06.