Important:
In addition to this section, you need to follow the Appurtenances requirements for all systems, WAC 296-826-50005.
or
You are exempt from the requirement not to install
EXEMPTION: | the shut off valve between the safety relief valve and the container or systems in the following situations: |
1. A three-way valve installed under two safety relief valves, each with: | |
a. The required rate of discharge; and | |
b. Installed to allow either of the safety relief valves to be closed off but not at the same time. | |
2. Two separate relief valves are installed with individual shut off valves. | |
3. The two shut off valve stems must be mechanically interconnected to allow the full required flow of one safety relief valve at all times. | |
4. When a safety relief valve manifold that allows: | |
a. One valve of two or more to be closed off ; and | |
b. The remaining valve or valves will provide not less than the rate of discharge shown on the manifold nameplate. |
Table 11
Appurtenances for Systems Mounted on Trucks, Semi-Trailers and Trailers
If you have: | Then make sure they: |
All container connections | Are provided with either of the following: 1. Automatic excess flow valves; or 2. Quick-closing internal valves that remain closed except during delivery operations. Note: If the control mechanism is provided with a secondary control remote from the delivery connection, then a fusible section (melting point 208°F to 220°F) is required to permit the internal valve to close automatically in case of fire. Exemption: Filling connections, safety relief devices, and liquid level and pressure gauge connections are exempt from automatic excess flow valves and quick-closing internal valves. |
Filling connections | Prevent back-flow in the event the filling connection breaks with at least one of the following: 1. Automatic back pressure check valves; 2. Excess flow check valves; 3. Quick closing internal valves. Exemption: An automatic valve is not required if: 1. The filling and discharge connect to a common opening in the container shell; and 2. The opening is fitted with a quick-closing internal valve. |
Nonrecessed container fittings and appurtenances | Are protected against physical damage by one of the following methods: 1. A protected location; 2. The vehicle frame or bumper. A protective housing that meets the following: 1. Is fabricated from material that is compatible with the containers design and construction requirements; 2. Designed to withstand static loadings in any direction equal to twice the weight of the container and attachments when filled using a safety factor of not less than 4, based on the ultimate strength of the material used. Note: Protect nonrecessed container fittings and appurtenances with a weather cover as needed for proper operation of valves and safety relief devices. |
Columnar-type gauges | 1. Are restricted to stationary storage installations. 2. Are shielded against the direct rays of the sun. 3. Are equipped with all of the following: a. Shut off valves having metallic hand-wheels; b. Excess flow valves; c. Extra heavy glass that is adequately protected with a metal housing applied by the gauge manufacturer. |
Hydrostatic relief valves | Are installed between each pair of valves in the liquid ammonia piping or hose. |
Wash. Admin. Code § 296-826-50020
Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, 49.17.060. 06-10-067, § 296-826-50020, filed 5/2/06, effective 9/1/06.