Indirect fired vaporizers utilizing steam, water, or other heating medium must be constructed and installed according to the following:
Exception: | When vaporizing and/or mixing equipment is in a structure not used exclusively for gas manufacturing or distribution, the structure or room must be separated from the remainder of the building. The separation must be a wall designed to withstand a static pressure of at least 100 pounds per square foot. This wall must have no openings or pipe or conduit passing through it. Such structure or room must have adequate ventilation and must have a roof or at least one exterior wall of lightweight construction. |
Exception: | This requirement does not apply to the domestic water heaters that may supply heat for a vaporizer in a domestic system. |
Wash. Admin. Code § 296-307-41027
Statutory Authority: RCW 49.17.040. 98-24-096, § 296-307-41027, filed 12/1/98, effective 3/1/99. 97-09-013, recodified as § 296-307-41027, filed 4/7/97, effective 4/7/97. Statutory Authority: RCW 49.17.040, [49.17.]050 and [49.17.]060. 96-22-048, § 296-306A-41027, filed 10/31/96, effective 12/1/96.