Wash. Admin. Code § 296-307-41025

Current through Register Vol. 24-23, December 1, 2024
Section 296-307-41025 - Safety devices
(1) Every container except those constructed according to DOT specifications and every vaporizer (except motor fuel vaporizers and vaporizers described in WAC 296-307-41029(3) and 296-307-42007(6)(a) whether heated by artificial means or not, must have one or more safety-relief valves of spring-loaded or equivalent type. These valves must be arranged to afford free vent to the outer air with discharge not less than five feet horizontally away from any opening into the building that is below such discharge. The rate of discharge must be according to the requirements of subsection (2) or (4) of this section.
(2) Minimum required rate of discharge in cubic feet per minute of air at one hundred twenty percent of the maximum permitted start to discharge pressure for safety-relief valves to be used on containers other than those constructed according to DOT specification must be as follows:

Surface area sq. ft.FlowrateCFMairSurface area sq. ft.Flow rate CFM airSurface area sq. ft.FlowrateCFMair
20 or less 626 170 3,620 550 9,470
25 751 175 3,700 600 10,170
30 872 180 3,790 650 10,860
35 990 185 3,880 700 11,550
40 1,100 190 3,960 750 12,220
45 1,220 195 4,050 850 13,540
50 1,330 200 4,130 900 14,190
55 1,430 210 4,300 950 14,830
60 1,540 220 4,470 1,000 15,470
65 1,640 230 4,630 1,050 16,100
70 1,750 240 4,800 1,100 16,720
75 1,850 250 4,960 1,150 17,350
80 1,950 260 5,130 1,200 17,960
85 2,050 270 5,290 1,250 18,570
90 2,150 280 5,450 1,300 19,180
95 2,240 290 5,610 1,350 19,780
100 2,340 300 5,760 1,400 20,380
105 2,440 310 5,920 1,450 20,980
110 2,530 320 6,080 1,500 21,570
115 2,630 330 6,230 1,550 22,160
120 2,720 340 6,390 1,600 22,740
125 2,810 350 6,540 1,650 23,320
130 2,900 360 6,690 1,700 23,900
135 2,990 370 6,840 1,750 24,470
140 3,080 380 7,000 1,800 25,050
145 3,170 390 7,150 1,850 25,620
150 3,260 400 7,300 1,900 26,180
155 3,350 450 8,040 1,950 26,750
160 3,440 500 8,760 2,000 27,310
165 3,530

Surface area = total outside surface area of container in square feet.

(3) When the surface area is not stamped on the name plate or when the marking is not legible, calculate the area with one of the following formulas:
(a) Hemispherical heads: Area = (equals) (overall length) X (outside diameter) X 3.1416.
(b) Other than hemispherical heads: Area = (equals) (overall length) + 0.3 (outside diameter) X (outside diameter) X 3.1416.

Note: This formula is not exact, but will give results within the limits of practical accuracy for the sole purpose of sizing relief valves.

(c) Spherical container: Area = (equals) (outside diameter)2 X 3.1416.
(d) Flow rate: CFM air = (equals) required flow capacity in cubic feet per minute of air at standard conditions, 60°F and atmospheric pressure (14.7 psia).

For containers with total outside surface area greater than 2,000 sq. ft., the formula is: Flow rate CFM air = (equals) 53.632 A0.82 where A = (equals) outside surface area of the container in square feet.

Valves not marked "air" have flow rate marking in cubic feet per minute of LP-gas. These can be converted to ratings in cubic feet per minute of air by multiplying the LP-gas ratings by factors listed below. Air flow ratings can be converted to ratings in cubic feet per minute of LP-gas by dividing the air ratings by the factors listed below.

AIR CONVERSION FACTORS

Container type 100 125 150 175 200
Air conversion factor 1. 162 1. 142 1. 113 1. 078 1. 010

(4) The minimum required rate of discharge for safety-relief valves for LP-gas vaporizers (steam heated, water heated, and direct fired) must be determined as follows:
(a) Obtain the total surface area by adding the surface area of vaporizer shell in square feet directly in contact with LP-gas and the heat exchanged surface area in square feet directly in contact with LP-gas.
(b) Obtain the minimum required rate of discharge in cubic feet of air per minute, at 60°F and 14.7 psia from subsection (2) of this section, for this total surface area.
(5) Container and vaporizer safety-relief valves must be set to start to discharge, with relation to the design pressure of the container, according to the following:

ContainersMinimum (percent)Maximum (percent)
ASME Code; Par. U-68, U-69-1949 and earlier editions 110 *125
ASME Code; Par. U-200, U-201-1949 edition 88 *100
ASME Code-1950, 1952, 1956, 1959, 1962, 1965 and 1968 (Division I) editions 88 *100
API-ASME Code-all editions 88 *100
DOT As prescribed in 49 C.F.R. Chapter I

*Manufacturers of safety-relief valves are allowed a plus tolerance not exceeding 10% of the set pressure marked on the valve.

(6) Safety-relief devices used with systems employing non-DOT containers must be constructed to discharge at not less than the rates shown in subsection (2) of this section, before the pressure is in excess of 120% of the maximum (not including the 10% referred to in subsection (5) of this section) permitted start-to-discharge pressure setting of the device.
(7) In high temperature areas, the employer must use a lower vapor pressure product or a higher designed pressure vessel to prevent the safety valves from opening. The tanks may be protected by cooling devices such as spraying, shading, or other means.
(8) Safety-relief valves must be arranged to minimize tampering. For external pressure setting or adjustment, the relief valves must have an approved sealable adjustment.
(9) Shut-off valves are prohibited between safety-relief devices and the container, equipment, or piping.

Exception: A shut-off valve may be used where the arrangement of the valve allows the required capacity flow through the safety-relief device.

(10) Safety-relief valves must have direct communication with the vapor space of the container.
(11) Each safety-relief valve must be plainly and permanently marked with the following:
(a) Container type of the pressure vessel on which the valve is designed to be installed;
(b) The pressure in psig at which the valve is set to discharge;
(c) The actual rate of discharge of the valve in cubic feet per minute of air at 60°F and 14.7 psia; and
(d) The manufacturer's name and catalog number.

For example: T200-250-4050 AIR: Indicates that the valve is suitable for use on a Type 200 container, that it is set to start to discharge at 250 psig; and that its rate of discharge is 4,050 cubic feet per minute of air.

(12) Safety-relief valve assemblies and their connections must be large enough to provide the required rate of flow for the container on which they are installed.
(13) A hydrostatic relief valve must be installed between each pair of shut-off valves on LP-gas liquid piping. The start-to-discharge pressure setting of such relief valves must be a maximum of 500 psig. The minimum setting on relief valves installed in piping connected to non-DOT containers must be 140% of the container relief valve setting. For piping connected to DOT containers, the minimum must be 400 psig. The relief valve should not be installed in the pump discharge piping if the same protection can be provided by installing the relief valve in the suction piping. The start-to-discharge pressure setting of such a relief valve, if installed on the discharge side of a pump, must exceed the maximum pressure permitted by the recirculation device in the system.
(14) The discharge from any safety-relief device must not terminate in or beneath any building.

Exception: This requirement does not apply to relief devices covered by WAC 296-307-41017(1), 296-307-41507(1), or 296-307-41509.

(15) Container safety-relief devices and regulator relief vents must be located at least five feet in any direction from air openings into sealed combustion system appliances or mechanical ventilation air intakes.

Wash. Admin. Code § 296-307-41025

Amended by WSR 20-21-091, Filed 10/20/2020, effective 11/20/2020

Statutory Authority: RCW 49.17.040. 98-24-096, § 296-307-41025, filed 12/1/98, effective 3/1/99. 97-09-013, recodified as § 296-307-41025, filed 4/7/97, effective 4/7/97. Statutory Authority: RCW 49.17.040, [49.17.]050 and[49.17.]060 . 96-22-048, § 296-306A-41025, filed 10/31/96, effective 12/1/96.