Table T
Minimum Depth of Clear Working Space in Front of Electric
Equipment
Conditions (ft) | |||
Nominal voltage to ground | (a) | (b) | (c) |
601 to 2,500 | 3 | 4 | 5 |
2,501 to 9,000 | 4 | 5 | 6 |
9,001 to 25,000 | 5 | 6 | 9 |
25,001 to 75kV1 | 6 | 8 | 10 |
Above 75kV1 | 8 | 10 | 12 |
Note: | Minimum depth of clear working space in front of electric equipment with a nominal voltage to ground above 25,000 volts may be the same as for 25,000 volts under conditions (a), (b) and (c) for installations built prior to April 16, 1981. |
Conditions: | (a) Exposed live parts on one side and no live or grounded parts on the other side of the working space, or exposed live parts on both sides guarded by suitable wood or other insulating materials. Insulated wire or insulated busbars operating at 300 volts or less are not considered live parts. (b) Exposed live parts on one side and grounded parts on the other side. Concrete, brick, or tile walls will be considered grounded surfaces. (c) Exposed live parts on both sides of the workspace (not guarded as in (a)) with the operator between. |
Elevation of Unguarded Energized Parts Above Working Space
Nominal voltage between phases | Minimum elevation |
601 to 7,500 | 8 feet 6 inches |
7,501 to 35,000 | 9 feet |
Over 35kV | 9 feet + 0.37 inches per kV above 35kV |
Note: | Minimum elevation may be 8 feet for installations built prior to April 16, 1981, if the nominal voltage between phases is in the range of 601-6600 volts. |
Wash. Admin. Code § 296-307-36230
Statutory Authority: RCW 49.17.040. 98-24-096, § 296-307-36230, filed 12/1/98, effective 3/1/99. 97-09-013, recodified as § 296-307-36230, filed 4/7/97, effective 4/7/97. Statutory Authority: RCW 49.17.040, [49.17.]050 and[49.17.]060 . 96-22-048, § 296-306A-36230, filed 10/31/96, effective 12/1/96.