Sufficient access and working space must be provided and maintained about all electric equipment to permit ready and safe operation and maintenance of such equipment.
Working Clearances
Nominal voltage | Minimum clear distance for condition (ft) | ||
to ground | (a) | (b) | (c) |
0-150 | 13 | 13 | 3 |
151-600 | 13 | 3-1/2 | 4 |
Conditions: | (a) Exposed live parts on one side and no live or grounded parts on the other side of the working space, or exposed live parts on both sides guarded by suitable wood or other insulating material. Insulated wire or insulated busbars operating at 300 volts or less are not considered live parts. (b) Exposed live parts on one side and grounded parts on the other side. (c) Exposed live parts on both sides of the workspace (not guarded as in (a)) with the operator between. |
Motor control center. An assembly of one or more enclosed sections having a common power bus and principally containing motor control units.