S.D. Admin. R. 61:08:05:21

Current through Register Vol. 51, page 67, December 16, 2024
Section 61:08:05:21 - Placement of safety valves

No stop valves shall be installed between a safety valve or relief valve and the boiler. On existing installations the safety or relief valve shall be mounted within three feet of the steam stop valve or an additional safety or relief valve shall be installed directly on the boiler.

S.D. Admin. R. 61:08:05:21

SL 1975, ch 16, § 1; 8 SDR 87, 8 SDR 134, effective 7/1/1982; 12 SDR 151, 12 SDR 155, effective 7/1/1986.

General Authority: SDCL 34-29A-16.

Law Implemented: SDCL 34-29A-24.