Section 44:75:14:24 - Emergency electrical circuit connections

Emergency electrical service shall be furnished to circuits as follows:

(1) Lighting of exit ways and all necessary ways of approach to them, including exit signs and exit direction signs, exterior of exits, exit doorways, stairways, and corridors;
(2) Surgical, obstetrical, and emergency room operating lights;
(3) Lighting for nursery, laboratory, recovery room, intensive care areas, nursing stations, medication preparation areas, and labor rooms;
(4) Lighting for the generator set location, the switch gear location, and the boiler room;
(5) Equipment essential to life safety and for protection of important equipment or vital materials;
(6) Nurses calling system;
(7) Alarm system, including fire alarms actuated at manual stations;
(8) Water flow alarm devices of sprinkler system if electrically operated;
(9) Fire detecting and smoke detecting systems;
(10) Paging or speaker systems if intended for issuing instructions during emergency conditions;
(11) Alarms required for nonflammable medical gas systems, if installed;
(12) Receptacles for incubators for infants;
(13) Pump for central suction system;
(14) Sewage or sump lift pump, if installed;
(15) Receptacles for blood bank refrigerator;
(16) At least two duplex receptacles for the laboratory;
(17) Receptacles in operating, recovery, intensive care, and delivery rooms except those for X ray;
(18) At least one duplex receptacle in each nursery;
(19) Duplex receptacles in patient corridors; and
(20) Equipment, such as burners and pumps, necessary for operation of one or more boilers required for heating and sterilization and their necessary auxiliaries and controls.