S.D. Admin. R. 20:10:39:35

Current through Register Vol. 51, page 67, December 16, 2024
Section 20:10:39:35 - Data collection for the 48 hour test

A digitizing data recorder with averaging capability and capable of detecting and recording transient deviations of one-tenth of a second or less in duration is used to record the following:

(1) Voltage from primary neutral at the transformer to remote reference electrode;
(2) Voltage from secondary neutral in the service panel serving the area of the cow contact to remote reference electrode;
(3) Voltage from primary neutral at the transformer to secondary neutral at the service panel serving the area of cow contact; and
(4) Cow contact current through or voltage across a shunt resistor at each high voltage point found in the cow contact test.

A recording interval as high as ten seconds may be used provided that transient deviations of voltage or current of one-tenth second or less in duration of voltage or current are recorded to the maximum ability of the instrument.

S.D. Admin. R. 20:10:39:35

42 SDR 174, effective 6/21/2016

General Authority: SDCL 49-47-2.

Law Implemented: SDCL 49-47-2, 49-47-3.