Compliance shall be demonstrated by either:
Add the following to R401.3 Certificate:
Figure R401.3 A certificate similar to this shall be attached to or near the electrical panel board | |||
ENERGY CERTIFICATE | |||
Street Address | |||
City / Town | |||
Predominant Values | |||
R-Value Ceiling / Roof | |||
R- Value Walls | |||
R- Value Ducts (outside conditioned space) | |||
U Factor Fenestration | |||
SHGC Fenestration | |||
Gas Fired Un-Vented Room Heater | |||
Baseboard Electric Heater | |||
Electric Furnace | |||
U Factor Skylight / SHGC | |||
AFUE Value Boiler / Furnace | |||
Efficiency and type of heating equipment | |||
Efficiency and type of cooling equipment | |||
Efficiency and type of service water heater | |||
Contractor or Design Professional | |||
Address | |||
Registration | |||
Duct Test Results | |||
Envelope Test Results ACH | |||
Date | Signature | ||
Delete and substitute Table R402.1.2:
TABLE R 402.1.2 INSULATION AND FENESTRATION REQUIREMENTS BY COMPONENT a | ||||||||||
CLIMATE ZONE | U-FACTOR b FENESTRATION | U-FACTOR SKYLIGHT b | GLAZED FERNESTRATION SHGC b | R-VALUE i CEILING | WOOD FRAME WALL R-VALUE g | R-VALUE MASS WALL | R-VALUE FLOOR | WALL R-VALUE BASEMENT C | R-VALUE & DEPTH SLAB d | R-VALUE CRAWL SPACE c WALL |
5 | 0.35 | 0.60 | NR | 38 | 20 or 13+5 f | 13/17 | 30 e | 10/13 | R-10 for 2 ft. | 10/13 |
For SI: 1 foot = 304.8 mm.
Delete and substitute TABLE R402.1. 4 EQUIVALENT U-FACTORS, a
CLIMATE ZONE | FENESTRATION U-FACTOR | SKYLIGHT U-FACTOR | CEILING U-FACTOR | FRAME WALL U-FACTOR | MASS WALL U-FACTORb | FLOOR U-FACTOR | BASEMENT WALL U-FACTOR | CRAWL SPACE WALL U-FACTOR |
5 | 0.30 | 0.55 | 0.026 | 0.060 | 0.082 | 0.033 | 0.050 | 0.055 |
During testing:
510 R.I. Code R. 510-RICR-00-00-8.11