Delete section R301 and substitute the following.
Section C301 Climate Zones
Table R301.1 Delete and substitute the following:
Table R301.1 Exterior Design Conditions | Value | Value |
Climate zone | Providence County | All others |
Winter, design dry-bulb (degree F) | 0 | 5 |
Summer, design dry-bulb | 87 | 89 |
Summer design wet-bulb | 71 | 73 |
Degree days heating | 6831 | 5950 |
Degree days cooling | 371 | 811 |
Delete without substitute section R301.2 and R301.3
Delete Table R301.3(1) without substitute
Delete Table R301.3(2) without substitute
Delete Figure R301.1 and substitute the following: figure R301.1
510 R.I. Code R. 510-RICR-00-00-8.10
Amended effective 2/1/2022