Ohio Admin. Code 3701:1-52-10

Current through all regulations passed and filed through October 28, 2024
Section 3701:1-52-10 - Fire protection
(A) The radiation room at a panoramic irradiator must have heat and smoke detectors. The detectors must activate an audible alarm. The alarm must be capable of alerting a person who is prepared to summon assistance promptly. The sources must automatically become fully shielded if a fire is detected.
(B) The radiation room at a panoramic irradiator must be equipped with a fire extinguishing system capable of extinguishing a fire without the entry of personnel into the room. The system for the radiation room must have a shut-off valve to control flooding into unrestricted areas.

Ohio Admin. Code 3701:1-52-10

Five Year Review (FYR) Dates: 4/19/2022 and 04/19/2027
Promulgated Under: 119.03
Statutory Authority: 3748.04
Rule Amplifies: 3748.04
Prior Effective Dates: 10/20/2002
Five Year Review (FYR) Dates: 10/25/2016 and 10/15/2021
Promulgated Under: 119.03
Statutory Authority: 3748.04
Rule Amplifies: 3748.04
Prior Effective Dates: 10/20/2002