N.D. Admin. Code 33.1-14-09-19

Current through Supplement No. 394, October, 2024
Section 33.1-14-09-19 - Modular hot water heating boilers
1. Individual modules must be limited to a maximum input of four hundred thousand British thermal units [4.22 x 10 to the eighth power joules] per hour (gas), three gallons [11.36 liters] per hour (oil), or one hundred fifteen kilowatt-hours (electricity).
2. Each module of a modular hot water heating boiler must be equipped with the following:
a. Pressure/altitude gauge (see section 33.1-14-09-12).
b. Thermometer (see section 33.1-14-09-13).
c. Operating temperature control (see subsection 2 of section 33.1-14-09-14).
d. Safety relief valve (see section 33.1-14-09-07).
e. Drain valve (see section 33.1-14-09-20).
3. The assembled modular hot water heating boiler must be equipped with the following:
a. High-limit temperature control (see subsection 1 of section 33.1-14-09-14).
b. Low-water fuel cutoff (see section 33.1-14-09-18).
c. Makeup feedwater connection (see section 33.1-14-09-11).
d. Expansion tank provisions (see section 33.1-14-09-15).
e. Stop valves (see section 33.1-14-09-10).

N.D. Admin Code 33.1-14-09-19

Adopted by Administrative Rules Supplement 2020-377, July 2020, effective 7/1/2020.

General Authority: NDCC 23.1-16

Law Implemented: NDCC 23.1-16