N.D. Admin. Code 33.1-14-09-12

Current through Supplement No. 394, October, 2024
Section 33.1-14-09-12 - Pressure or altitude gauges
1. Each hot water boiler must have a pressure or altitude gauge connected to it or to its flow connection in such a manner that it cannot be shut off from the boiler except by a cock with tee or lever handle placed on the pipe near the gauge. The handle of the cock must be parallel to the pipe in which it is located when the cock is open.
2. The scale on the dial of the pressure or altitude gauge must be graduated to not less than one and one-half nor more than three and one-half times the pressure at which the safety relief valve is set. The gauge must be provided with effective stops for the indicating pointer at the zero point and at the maximum pressure point.
3. Piping or tubing for pressure or altitude gauge connections must be of nonferrous metal when smaller than one inch [25.4 millimeter] pipe size.

N.D. Admin Code 33.1-14-09-12

Adopted by Administrative Rules Supplement 2020-377, July 2020, effective 7/1/2020.

General Authority: NDCC 23.1-16