N.Y. Comp. Codes R. & Regs. Tit. 6 §§ 227-3.4

Current through Register Vol. 46, No. 45, November 2, 2024
Section 227-3.4 - Control requirements
(a) The following NOx emission limits on a parts per million dry volume basis (ppmvd), corrected to 15 percent oxygen must be met as a facility-level weighted average of all applicable SCCTs at a facility:
(1) By May 1, 2023:

NOx Emission Limit (ppmvd)
All SCCTs100

(2) By May 1, 2025:

Fuel TypeNOx Emission Limit (ppmvd)
Gaseous fuels25
Distillate oil or other liquid fuel42

(3) Compliance with these emission limits must be determined by conducting stack tests, as set forth in section 227-2.6(c) of this Title, at a minimum of once per permit term. Alternatively, the owner or operator may choose to use a continuous emissions monitoring system (CEMS) consistent with the provisions of section 227-2.6(b) of this Title.

N.Y. Comp. Codes R. & Regs. Tit. 6 §§ 227-3.4

Adopted New York State Register December 31, 2019/Volume XLI, Issue 53, eff. 1/11/2020