N.Y. Comp. Codes R. & Regs. Tit. 12 §§ 4-11.5

Current through Register Vol. 46, No. 50, December 11, 2024
Section 4-11.5 - Automatic-maximum firing rate over 16 to 33 gallons per hour

The main flame trial-for-ignition period shall not exceed 15 seconds and the main flame shall be continually supervised while the burner is firing. Upon flame failure, the main oil valve shall close automatically within 15 seconds if the burner does not relight within this time.