The main flame trial-for-ignition period shall not exceed 30 seconds and the main flame shall be continually supervised while the burner is firing. Upon flame failure, the main oil valve shall close automatically within 30 seconds if the burner does not relight within this time.
N.Y. Comp. Codes R. & Regs. Tit. 12 §§ 4-11.4