229 Neb. Admin. Code, ch. 4, § 012

Current through September 17, 2024
Section 229-4-012

All boiler rooms exceeding five hundred square feet floor area and containing one (1) or more gas fired objects having a fuel burning capacity in excess of 400,000 Btu/hr shall have two (2) means of exit.

Condensate return tanks shall be equipped with at least two (2) vents or a vent and overflow pipe to protect against a loose float plugging a single connection.

229 Neb. Admin. Code, ch. 4, § 012

Amended effective 8/7/2016.