La. Admin. Code tit. 51 § XIV-713

Current through Register Vol. 50, No. 11, November 20, 2024
Section XIV-713 - Connections between Drainage Piping and Fixtures
A. Connections between drainage piping and floor outlet plumbing fixtures shall be made by means of an approved flange which is attached to the drainage piping in accordance with the provisions of this Chapter. The 4 x 3 closet flange shall be attached to the outside diameter and not to the inside diameter of the drainage piping. The floor flange shall be set on and securely anchored to the building structure.
B. Connections between drainage piping and wall hung water closets shall be made by means of an approved extension nipple or horn adapter.
C. The connection shall be bolted to the flange or carrier using corrosion resisting bolts, screws or assemblies recommended by the manufacturer.
D. An approved gasket, washer, or setting compound shall be used between the fixture and the connection. Use of commercial putty or plaster shall be prohibited as the setting compound.

La. Admin. Code tit. 51, § XIV-713

Promulgated by the Department of Health and Hospitals, Office of Public Health, LR 38:2850 (November 2012).
AUTHORITY NOTE: Promulgated in accordance with R.S. 40:4(A)(7) and R.S. 40:5(2)(3)(7)(9)(16)(17)(20).