La. Admin. Code tit. 43 § XIII-7915

Current through Register Vol. 50, No. 11, November 20, 2024
Section XIII-7915 - Isolating and Purging [49 CFR 193.2615]
A. Before personnel begin maintenance activities on components handling flammable fluids which are isolated for maintenance, the component must be purged in accordance with a procedure which meets the requirements of "Purging Principles and Practices (incorporated by reference, see LAC 43:XIII.6713)"; unless the maintenance procedures under LAC 43:XIII.7905 provide that the activity can be safely performed without purging. [ 49 CFR 193.2615(a) ]
B. If the component or maintenance activity provides an ignition source, a technique in addition to isolation valves (such as removing spool pieces or valves and blank flanging the piping, or double block and bleed valving) must be used to ensure that the work area is free of flammable fluids. [ 49 CFR 193.2615(b) ]

La. Admin. Code tit. 43, § XIII-7915

Promulgated by the Department of Natural Resources, Office of Conservation, LR 441056 (6/1/2018).
AUTHORITY NOTE: Promulgated in accordance with R.S. 30:551.C.