La. Admin. Code tit. 43 § XIII-1161

Current through Register Vol. 50, No. 11, November 20, 2024
Section XIII-1161 - Required Capacity of Pressure Relieving and Limiting Stations [49 CFR 192.201]
A. Each pressure relief station or pressure limiting station or group of those stations installed to protect a pipeline must have enough capacity, and must be set to operate, to insure the following: [ 49 CFR 192.201(a)]
1. in a low pressure distribution system, the pressure may not cause the unsafe operation of any connected and properly adjusted gas utilization equipment; [ 49 CFR 192.201(a)(1)]
2. in pipelines other than a low pressure distribution system: [ 49 CFR 192.201(a)(2)]
a. if the maximum allowable operating pressure is 60 psi (414 kPa) gage or more, the pressure may not exceed the maximum allowable operating pressure plus 10 percent, or the pressure that produces a hoop stress of 75 percent of SMYS, whichever is lower; [ 49 CFR 192.201(a)(2)(i)]
b. if the maximum allowable operating pressure is 12 psi (83 kPa) gage or more, but less than 60 psi (414 kPa) gage, the pressure may not exceed the maximum allowable operating pressure plus 6 psi (41 kPa) gage; or [ 49 CFR 192.201(a)(2)(ii) ]
c. if the maximum allowable operating pressure is less than 12 psi (83 kPa) gage, the pressure may not exceed the maximum allowable operating pressure plus 50 percent. [ 49 CFR 192.201(a)(2)(iii) ]
B. When more than one pressure regulating or compressor station feeds into a pipeline, relief valves or other protective devices must be installed at each station to ensure that the complete failure of the largest capacity regulator or compressor, or any single run of lesser capacity regulators or compressors in that station, will not impose pressures on any part of the pipeline or distribution system in excess of those for which it was designed, or against which it was protected, whichever is lower. [ 49 CFR 192.201(b)]
C. Relief valves or other pressure limiting devices must be installed at or near each regulator station in a low-pressure distribution system, with a capacity to limit the maximum pressure in the main to a pressure that will not exceed the safe operating pressure for any connected and properly adjusted gas utilization equipment. [ 49 CFR 192.201(c)]

La. Admin. Code tit. 43, § XIII-1161

Promulgated by the Department of Natural Resources, Office of Conservation, LR 9:228 (April 1983), amended LR 10:520 (July 1984), LR 27:1541 (September 2001), LR 30:1240 (June 2004).
AUTHORITY NOTE: Promulgated in accordance with R.S. 30:501 et seq.