46 C.F.R. § 111.60-2

Current through November 30, 2024
Section 111.60-2 - Specialty cable for communication and RF applications

Specialty cable such as certain coaxial cable that cannot pass the flammability test contained in IEEE 1580, test FV-2/VW-1 of ANSI/UL 2556, IEC 60332-3-21:2018, or IEC 60332-3-22:2018 (all incorporated by reference; see § 110.10-1 of this subchapter) because of unique properties of construction, must:

(a) Be installed physically separate from all other cable; and
(b) Have fire stops installed-
(1) At least every 7 meters (21.5 feet) vertically, up to a maximum of 2 deck heights;
(2) At least every 15 meters (46 feet) horizontally;
(3) At each penetration of an A or B Class boundary;
(4) At each location where the cable enters equipment; or
(5) In a cableway that has an A-60 fire rating.

46 C.F.R. §111.60-2

CGD 94-108, 61 FR 28280, June 4, 1996, as amended by USCG-2003-16630, 73 FR 65198 , Oct. 31, 2008; USCG-2013-0671, 78 FR 60153 , Sept. 30, 2013