46 C.F.R. § 111.60-1

Current through September 30, 2024
Section 111.60-1 - Construction and testing of cable
(a) Electric cables constructed of stranded copper conductors, thermoplastic, elastomeric or other insulation, moisture-resistant jackets, and, where applicable, armoring and outer-sheathing must meet all the requirements of IEC 60092-350:2014, 60092-352:2005, 60092-353:2016, 60092-354:2014, 60092-360:2014, IEC/TR 60092-370:2009, 60092-376:2017, IEEE 1580, ANSI/UL 1072, ANSI/UL 1309, or MIL-DTL-24640C or MIL-DTL-24643C (all incorporated by reference; see § 110.10-1 of this subchapter), including the respective flammability tests contained therein.
(b) IEC 60092 series cable must meet the Category A or A F/R flammability requirements of IEC 60332-3-22:2009 or 60332-3-21:2000 (both incorporated by reference; see § 110.10-1 of this subchapter).

46 C.F.R. §111.60-1

USCG-2003-16630, 73 FR 65198, Oct. 31, 2008, as amended by USCG-2013-0671, 78 FR 60153, Sept. 30, 2013
88 FR 16363, 4/17/2023