10 C.F.R. § 434.403

Current through October 31, 2024
Section 434.403 - Building mechanical systems and equipment

Mechanical systems and equipment used to provide heating, ventilating, and air conditioning functions as well as additional functions not related to space conditioning, such as, but not limited to, freeze protection in fire projection systems and water heating, shall meet the requirements of this section.

403.1Mechanical Equipment Efficiency. When equipment shown in Tables 403.1a through 403.1f is used, it shall have a minimum performance at the specified rating conditions when tested in accordance with the specified reference standard. The reference standards listed in Tables 403.1a through 403.1f are incorporated by reference, see § 434.701 . Omission of minimum performance requirements for equipment not listed in Tables 403.1a through 403.1f does not preclude use of such equipment.

Table 403.1a-Unitary Air Conditioners and Condensing Units, Electrically Operated, Minimum Efficiency Requirements

Equipment typeSize category Subcategory or rating condition Minimum
Efficiency2
Test
procedure1
Air Conditioners, Air Cooled[LESS THAN]65,000 Btu/hSplit system
Single Package
10.0 SEER
9.7 SEER
ARI 210/240
(RS-15)*
[GREATER THAN EQUAL TO]65,000 Btu/h and [LESS THAN]135,00
Btu/h
Split System and Single Package8.9 EER3
8.3 IPLV3
ARI 210/240
(RS-15)*
[GREATER THAN EQUAL TO]135,000 Btu/h and [LESS THAN]240,000 Btu/hSplit System and Single Package8.5 EER3
7.5 IPLV3
[GREATER THAN EQUAL TO]240,000 Btu/h and [LESS THAN]760,000 Btu/hSplit System and Single Package8.5 EER3
7.5 IPLV3
ARI-340/360
(RS-16)*
[GREATER THAN EQUAL TO]760,000 Btu/hSplit System and Package8.3 EER3
7.5 IPLV3
ARI-340/360
(RS-16)*
Air Conditioners, Water and Evaporatively Cooled[LESS THAN]65,000 Btu/hSplit System and Single Package9.3 EER3
8.4 IPLV3
ARI 210/240
(RS-15)*
[GREATER THAN EQUAL TO]65,000 Btu/h and [LESS THAN]135,000 Btu/hSplit System and Single Package10.5 EERc
9.7 IPLVc
ARI 210/240
(RS-15)*
[GREATER THAN EQUAL TO]135,000 Btu/h and [LESS THAN]240,000 Btu/hSplit System and Single Package9.6 EERc
9.0 IPLVc
ARI-340/360
(RS-16)*
[GREATER THAN EQUAL TO]240,000 Btu/hSplit System and Single Package9.6 EERc
9.0 IPLVc
ARI-340/360
(RS-16)*
Condensing Units, Air Cooled135,000 Btu/h9.9 EER
11.0 IPLV
ARI 365
(RS-29)*
Condensing Units, Water or Evaporatively Cooled135,000 Btu/h12.9 EER
12.9 IPLV
ARI 365
(RS-29)*

1 See subpart E for detailed references

2 IPLVs are only applicable to equipment with capacity modulation.

3 Deduct 0.2 from the required EERs and IPLVs for units that have a heating section.

* Incorporation by reference, see § 434.701

Table 403.1b-Unitary and Applied Heat Pumps, Electrically Operated, Minimum Efficiency Requirements

Equipment typeSize category Subcategory or rating condition Minimum efficiency2Test procedure1
Air Cooled (Cooling Mode)[LESS THAN]65,000 Btu/hSplit System
Single Package
10.0 SEER
9.7 SEER
ARI 210/240
(RS-15)*
[GREATER THAN EQUAL TO]65,000 Btu/h and [LESS THAN]135,000 Btu/hSplit System and Single Package8.9 EER3
8.3 IPLV3
ARI 210/240
(RS-15)*
[GREATER THAN EQUAL TO]135,000 Btu/h and [LESS THAN]240,000 Btu/hSplit System and Single Package8.5 EER3
7.5 IPLV3
ARI-340/360
(RS-16)*
[GREATER THAN EQUAL TO]240,000 Btu/hSplit System and Single Package8.5 EER3
7.5 IPLV3
ARI-340/360
(RS-16)*
Water Source
(Cooling Mode)
[LESS THAN]65,000 Btu/h85 °F Entering Water
75 °F Entering Water
9.3 EER
10.2 EER
ARI-320
(RS-27)*
[GREATER THAN EQUAL TO]65,000 Btu/h and [LESS THAN]135,000
Btu/h
85 °F Entering Water
75 °F Entering Water
10.5 EER
11.0 EER
ARI-320
(RS-27)*
Groundwater-Source (Cooling Mode)[LESS THAN]135,000 Btu/h70 F Entering Water
50 F Entering Water
11.0 EER
11.5 EER
ARI 325
(RS-28)*
Ground Source (Cooling Mode)[LESS THAN]135,000 Btu/h77 F Entering Water
70 F Entering Water
10.0 EER
10.4 EER
ARI 325
(RS-28)*
Air Cooled (Heating Mode)[LESS THAN]65,000 Btu/h (Cooling Capacity)Split System
Single Package
6.8 HSPF
6.6 HSPF
ARI 210/240
(RS-15)*
65,000 Btu/h and [LESS THAN]135,000 Btu/h (Cooling Capacity)47 F db/43 F wb Outdoor Air
17 F db/15 F wb Outdoor Air
3.00 COP
2.00 COP
ARI 210/240
(RS-15)*
135,000 Btu/h (Cooling Capacity)47 F db/43 F wb Outdoor Air
17 F db/15 F wb Outdoor
2.90 COP
2.00 COP
ARI-340/360
(RS-1/)*
Water-Source (Heating Mode)[LESS THAN]135,000 Btu/h (Cooling Capacity)70 F Entering Water
75 F Entering Water
3.80 COP
3.90 COP
ARI-320
(RS-27)*
Groundwater-Source (Heating Mode)[LESS THAN]135,000 Btu/h (Cooling Capacity)70 F Entering Water
50 F Entering Water
3.40 COP
3.00 COP
ARI 325
(RS-28)*
Ground Source (Heating Mode)[LESS THAN]135,000 Btu/h (Cooling Capacity)32 F Entering Water
41 F Entering Water
2.50 EER
2.70 EER
ARI-330
(RS-45)*

1 See subpart E for detailed references.

2 IPLVs are only applicable to equipment with capacity modulation.

3 Deduct 0.2 from the required EERs and IPLVs for units that have a heating section.

* Incorporation by reference, see § 434.701 .

Table 403.1c-Water Chilling Packages, Minimum Efficiency Requirements

Equipment typeSize category Subcategory or rating condition Minimum efficiency2Test procedure1
Air-Cooled, With Condenser, Electrically Operated[LESS THAN]150 Tons
[GREATER THAN EQUAL TO]150 Tons
2.70 COP
2.80 IPLV
2.50 COP
2.50 IPLV
ARI 550 Centrifugal/Rotary Screw (RS-30)* or ARI 590 Reciprocating (RS-31)*
Air-Cooled, Without Condenser, Electrically OperatedAll Capacities3.10 COP
3.20 IPLV
Water Cooled, Electrically Operated, Positive Displacement (Reciprocating)All Capacities3.80 COP
3.90 IPLV
Water Cooled, Electrically Operated, Positive Displacement (Rotary Screw and Scroll)[LESS THAN]150 Tons
[GREATER THAN EQUAL TO]150 Tons and [LESS THAN]300 Tons
[GREATER THAN EQUAL TO]300 Tons

3.80 COP
3.90 IPLV
4.20 COP
4.50 IPLV
5.20 COP
5.30 IPLV
Water-Cooled, Electrically Operated, Centrifugal[LESS THAN]150 Tons
150 Tons and [LESS THAN]300 Tons
300 Tons

3.80 COP
3.90 IPLV
4.20 COP
4.50 IPLV
5.20 COP
5.30 IPLV
ARI 550
(RS-30)*
Absorption Single EffectAll Capacities0.48 COP
Absorption Double Effect, Indirect-FiredAll Capacities0.95 COP
1.00 IPLV
ARI 560
(RS-46)*
Absorption Double-Effect, Direct-FiredAll Capacities0.95 COP
1.00 IPLV

1 See subpart E for detailed references.

2 Equipment must comply with all efficiencies when multiple efficiencies are indicated.

*Incorporation by reference, see § 434.701 .

Table 403.1d-Packaged Terminal Air Conditioners, Packaged Terminal Heat Pumps, Room Air Conditioners, and Room Air-Conditioner Heat Pumps Electrically Operated, Minimum Efficiency Requirements

Equipment typeSize category Subcategory or rating condition Minimum efficiency2Test procedure1
PTAC (Cooling Mode)All Capacities95 °F db Outdoor Air
82 °F db Outdoor Air
10.0 - (0.16 * Cap/1,000)3EER
12.2 - (0.20 * Cap/1,000)3EER
ARI 310/380
(RS-17)*
ARI 310/380
(RS-17)*
PTHP (Cooling Mode)All Capacities95 °F db Outdoor Air
82 °F db Outdoor Air
10.0-(0.16 * Cap/1,000)3 EER
12.2-(0.20 * Cap/1,000) EER
PTHP (Heating Mode)All Capacities2.90-(0.026 * CAP/1,000)3 COP
Room Air Conditioners, With Louvered Sides[LESS THAN]6,000 Btu/h
[GREATER THAN EQUAL TO]6,000 Btu/h and [LESS THAN]8,000 Btu/h
[GREATER THAN EQUAL TO]8,000 Btu/h and [LESS THAN]14,000 Btu/h
[GREATER THAN EQUAL TO]14,000 Btu/h and [LESS THAN]20,000 Btu/h
[GREATER THAN EQUAL TO]20,000 Btu/h
8.0 EER
8.5 EER
9.0 EER
8.8 EER
8.2 EER
ANSI/AHAM RAC-1
(RS-40)*
Room Air Conditioner, Without Louvered Sides[LESS THAN]6,000 Btu/h
[GREATER THAN EQUAL TO]6,000 Btu/h and [LESS THAN]20,000 Btu/h
[GREATER THAN EQUAL TO]20,000 Btu/h
8.0 EER
8.5 EER
8.2 EER
ANSI/AHAM RAC-1
(RS-40)*
Room Air-Conditioner Heat Pumps With Louvered SidesAll Capacities8.5 EERANSI/AHAM RAC-1
(RS-40)*
Room Air-Conditioner Heat Pumps Without Louvered SidesAll Capacities8.0 EERANSI/AHAM RAC-1
(RS-40*

1 See subpart E for detailed references.

2 Equipment must comply with all efficiencies when multiple efficiencies are indicated. (Note products covered by the 1992 Energy Policy Act have no efficiency requirement for operation at other than standard rating conditions for products manufactured after 1/1/94).

3 Cap means the rated capacity of the product in Btu/h. If the unit's capacity is less than 7,000 Btu/h, use 7,000 Btu/h in the calculation. If the unit's capacity is greater than 15,000 Btu/h, use 15,000 Btu/h in the calculation.

* Incorporation by reference, see § 434.701 .

Table 403.1e-Warm Air Furnaces and Combination Warm Air Furnaces/Air Conditioning Units, Warm Air Duct Furnaces and Unit Heaters, Minimum Efficiency Requirements

Equipment typeSize category Subcategory or rating condition Minimum efficiencyb eTest procedurea
Warm Air-Furnace, Gas-Fired[LESS THAN]225,000 Btu/h78% AFUE or 80% EtDOE 10 CFR 430
Appendix N
[GREATER THAN EQUAL TO]225,000 Btu/hMaximum Capacityc
Minimum Capacityc
80% Et
78% Et
ANSI Z21.47
(RS-21)*
Warm Air-Furnace, Oil-Fired[LESS THAN]225,000 Btu/h78% AFUE or 80% EtdDOE 10 CFR 430
Appendix N
[GREATER THAN EQUAL TO]225,000 But/hMaximum Capacityc
Minimum Capacity
81% Et
81% Et
U.L. 727
(RS-22)*
Warm Air Duct Furnaces, Gas-FiredAll CapacitiesMaximum Capacityc
Minimum Capacity
78% Et
75% Et
ANSI Z83.9
(RS-23)
Warm Air Unit Heaters, Gas FiredAll CapacitiesMaximum Capacityc
Minimum Capacity
78% Et
74% Et
ANSI Z83.8
(RS-24)*
Oil-FiredAll CapacitiesMaximum Capacityc
Minimum Capacity
81% Et
81% Et
U.L. 731
(RS-25)*

a See subpart E for detailed references.

b Minimum and maximum ratings as provided for and allowed by the unit's controls.

c Combination units not covered by NAECA (Three-phase power or cooling capacity [GREATER THAN EQUAL TO]65,000 Btu/h) may comply with either rating.

d Et = thermal efficiency. See referenced document for detailed discussion.

e Ec = combustion efficiency. Units must also include an IID and either power venting or a flue damper. For those furnaces where combustion air is drawn from the conditioned space, a vent damper may be substituted for a flue damper.

* Incorporation by reference, see § 434.701

Table 403.1f-Boilers, Gas- and Oil-Fired, Minimum Efficiency Requirements

Equipment typeSize category Subcategory or rating condition Minimum efficiencybTest procedurea
Boilers, Gas-Fired[LESS THAN]300,000 Btu/hHot Water80% AGUEDOE 10 CFR 430
Appendix N
Steam75% AGUEDOE 10 CFR 430
Appendix N
[LESS THAN]300,000 Btu/hMaximum Capacityc
Minimum Capacity
80% Ec
80% Ec
ANSI Z21.13
(RS-32)*
Boilers, Oil-Fired[LESS THAN]300,000 Btu/h80% AGUEDOE 10 CFR 430
(RS-20)*
[LESS THAN]300,000 Btu/hMaximum Capacityc
Minimum Capacity
83% Ec
83% Ec
U.L. 726
(RS-33)*
Oil-Fired (Residual)[LESS THAN]3000,000 Btu/hMaximum Capacityc
Minimum Capacity
83% Ec
83% Ec

a See subpart E for detailed references.

b Minimum and maximum ratings as provided for and allowed by the unit's controls.

c Ec = combustion efficiency (100% less flue losses). See reference document for detailed information.

* Incorporation by reference, see § 434.701 .

403.1.1 Where multiple rating conditions and/or performance requirements are provided, the equipment shall satisfy all stated requirements.
403.1.2 Equipment used to provide water heating functions as part of a combination integrated system shall satisfy all stated requirements for the appropriate space heating or cooling category.
403.1.3 The equipment efficiency shall be supported by data furnished by the manufacturer or shall be certified under a nationally recognized certification program or rating procedure.
403.1.4 Where components, such as indoor or outdoor coils, from different manufacturers are used, the system designer shall specify component efficiencies whose combined efficiency meets the standards herein.
403.2HVAC Systems.
403.2.1Load Calculations. Heating and cooling system design loads for the purpose of sizing systems and equipment shall be determined in accordance with the procedures described in RS-1 (incorporated by reference, see § 434.701 ) using the design parameters specified in subpart C of this part.
403.2.2Equipment and System Sizing. Heating and cooling equipment and systems shall be sized to provide no more than the loads calculated in accordance with subsection 403.2.1 . A single piece of equipment providing both heating and cooling must satisfy this provision for one function with the other function sized as small as possible to meet the load, within available equipment options. Exceptions are as follows:
(a) When the equipment selected is the smallest size needed to meet the load within available options of the desired equipment line.
(b) Standby equipment provided with controls and devices that allow such equipment to operate automatically only when the primary equipment is not operating.
(c) Multiple units of the same equipment type with combined capacities exceeding the design load and provided with controls that sequence or otherwise optimally control the operation of each unit based on load.
403.2.3Separate Air Distribution System. Zones with special process temperature and/or humidity requirements shall be served by air distribution systems separate from those serving zones requiring only comfort conditions or shall include supplementary provisions so that the primary systems may be specifically controlled for comfort purposes only. Exceptions: Zones requiring only comfort heating or comfort cooling that are served by a system primarily used for process temperature and humidity control need not be served by a separate system if the total supply air to these comfort zones is no more than 25% of the total system supply air or the total conditioned floor area of the zones is less than 1000 ft2.
403.2.4Ventilation and Fan System Design. Ventilation systems shall be designed to be capable of reducing the supply of outdoor air to the minimum ventilation rates required by Section 6.1.3 of RS-41 (incorporated by reference, see § 434.701 ) through the use of return ducts, manually or automatically operated control dampers, fan volume controls, or other devices. Exceptions are as follows: Minimum outdoor air rates may be greater if:
(a) Required to make up air exhausted for source control of contaminants such as in a fume hood.
(b) Required by process systems.
(c) Required to maintain a slightly positive building pressure. For this purpose, minimum outside air intake may be increased up to no greater than 0.30 air changes per hour in excess of exhaust quantities.
403.2.4.1Ventilation controls for variable or high occupancy areas. Systems with design outside air capacities greater than 3,000 cfm serving areas having an average design occupancy density exceeding 100 people per 1,000 ft2 shall include means to automatically reduce outside air intake to the minimum values required by RS-41 (incorporated by reference, see § 434.701 ) during unoccupied or low-occupancy periods. Outside air shall not be reduced below 0.14 cfm/ft2. Outside air intake shall be controlled by one or more of the following:
(a) A clearly labeled, readily accessible bypass timer that may be used by occupants or operating personnel to temporarily increase minimum outside air flow up to design levels.
(b) A carbon dioxide (CO2) control system having sensors located in the spaces served, or in the return air from the spaces served, capable of maintaining space CO2 concentrations below levels recommended by the manufacturer, but no fewer than one sensor per 25,000 ft2 of occupied space shall be provided.
(c) An automatic timeclock that can be programmed to maintain minimum outside air intake levels commensurate with scheduled occupancy levels.
(d) Spaces equipped with occupancy sensors.
403.2.4.2Ventilation Controls for enclosed parking garages. Garage ventilation fan systems with a total design capacity greater than 30,000 cfm shall have automatic controls that stage fans or modulate fan volume as required to maintain carbon monoxide (CO) below levels recommended in RS-41.
403.2.4.3Ventilation and Fan Power. The fan system energy demand of each HVAC system at design conditions shall not exceed 0.8 W/cfm of supply air for constant air volume systems and 1.25 W/cfm of supply air for variable-air-volume (VAV) systems. Fan system energy demand shall not include the additional power required by air treatment or filtering systems with pressure drops over 1 in. w.c. Individual VAV fans with motors 75 hp and larger shall include controls and devices necessary for the fan motor to demand no more than 30 percent of design wattage at 50 percent of design air volume, based on manufacturer's test data. Exceptions are as follows:
(a) Systems with total fan system motor horsepower of 10 hp or less.
(b) Unitary equipment for which the energy used by the fan is considered in the efficiency ratings of subsection 403.1 .
403.2.5Pumping System Design. HVAC pumping systems used for comfort heating and/or comfort air conditioning that serve control valves designed to modulate or step open and closed as a function of load shall be designed for variable fluid flow and capable of reducing system flow to 50 percent of design flow or less. Exceptions are as follows:
(a) Systems where a minimum flow greater than 50% of the design flow is required for the proper operation of equipment served by the system, such as chillers.
(b) Systems that serve no more than one control valve.
(c) Systems with a total pump system horse power [LESS THAN EQUAL TO]10 hp.
(d) Systems that comply with subsection 403.2.6.8 without exception.
403.2.6Temperature and Humidity Controls.
403.2.6.1System Controls. Each heating and cooling system shall include at least one temperature control device.
403.2.6.2Zone Controls. The supply of heating and cooling energy to each zone shall be controlled by individual thermostatic controls responding to temperature within the zone. For the purposes of this section, a dwelling unit is considered a zone. Exceptions are as follows: Independent perimeter systems that are designed to offset building envelope heat losses or gains or both may serve one or more zones also served by an interior system when the perimeter system includes at least one thermostatic control zone for each building exposure having exterior walls facing only one orientation for at least 50 contiguous ft and the perimeter system heating and cooling supply is controlled by thermostat(s) located within the zone(s) served by the system.
403.2.6.3Zone Thermostatic Control Capabilities. Where used to control comfort heating, zone thermostatic controls shall be capable of being set locally or remotely by adjustment or selection of sensors down to 55 °F or lower. Where used to control comfort cooling, zone thermostatic controls shall be capable of being set locally or remotely by adjustment or selection of sensors up to 85 °F or higher. Where used to control both comfort heating and cooling, zone thermostatic controls shall be capable of providing a temperature range or deadband of at least 5 °F within which the supply of heating and cooling energy to the zone is shut off or reduced to a minimum. Exceptions are as follows:
(a) Special occupancy or special usage conditions approved by the building official or
(b) Thermostats that require manual changeover between heating and cooling modes.
403.2.6.4Heat Pump Auxiliary Heat. Heat pumps having supplementary electric resistance heaters shall have controls that prevent heater operation when the heating load can be met by the heat pump. Supplemental heater operation is permitted during outdoor coil defrost cycles not exceeding 15 minutes.
403.2.6.5Humidistats. Humidistats used for comfort purposes shall be capable of being set to prevent the use of fossil fuel or electricity to reduce relative humidity below 60% or increase relative humidity above 30%.
403.2.6.6Simultaneous Heating and Cooling. Zone thermostatic and humidistatic controls shall be capable of operating in sequence the supply of heating and cooling energy to the zone. Such controls shall prevent: Reheating; recooling; mixing or simultaneous supply of air that has been previously mechanically heated and air that has been previously cooled, either by mechanical refrigeration or by economizer systems; and other simultaneous operation of heating and cooling systems to the same zone. Exceptions are as follows:
(a) Variable-air-volume systems that, during periods of occupancy, are designed to reduce the air supply to each zone to a minimum before heating, recooling, or mixing takes place. This minimum volume shall be no greater than the larger of 30% of the peak supply volume, the minimum required to meet minimum ventilation requirements of the Federal agency. (0.4 cfm/ft2 of zone conditioned floor area, and 300 cfm).
(b) Zones where special pressurization relationships or cross-contamination requirements are such that variable-air-volume systems are impractical, such as isolation rooms, operating areas of hospitals and clean rooms.
(c) At least 75% of the energy for reheating or for providing warm air in mixing systems is provided from a site-recovered or site-solar energy source.
(d) Zones where specified humidity levels are required to satisfy process needs, such as computer rooms and museums.
(e) Zones with a peak supply air quantity of 300 cfm or less.
403.2.6.7Temperature Reset for Air Systems. Air systems supplying heated or cooled air to multiple zones shall include controls that automatically reset supply air temperatures by representative building loads or by outside air temperature. Temperature shall be reset by at least 25% of the design supply air to room air temperature difference. Zones that are expected to experience relatively constant loads, such as interior zones, shall be designed for the fully reset supply temperature. Exception are as follows: Systems that comply with subsection 403.2.6.6 without using exceptions (a) or (b).
403.2.6.8Temperature Reset for Hydronic Systems. Hydronic systems of at least 600,000 Btu/hr design capacity supplying heated and/or chilled water to comfort conditioning systems shall include controls that automatically reset supply water temperatures by representative building loads (including return water temperature) or by outside air temperature. Temperature shall be reset by at least 25% of the design supply-to-return water temperature difference. Exceptions are as follows:
(a) Systems that comply with subsection 403.2.5 without exception or
(b) Where the design engineer certifies to the building official that supply temperature reset controls cannot be implemented without causing improper operation of heating, cooling, humidification, or dehumidification systems.
403.2.7Off Hour Controls.
403.2.7.1Automatic Setback or Shutdown Controls. HVAC systems shall be equipped with automatic controls capable of accomplishing a reduction of energy use through control setback or equipment shutdown. Exceptions are as follows:
(a) Systems serving areas expected to operate continuously or
(b) Equipment with full load demands not exceeding 2 kW controlled by readily accessible, manual off-hour controls.
403.2.7.2Shutoff Dampers. Outdoor air supply and exhaust systems shall be provided with motorized or gravity dampers or other means of automatic volume shutoff or reduction. Exceptions are as follows:
(a) Systems serving areas expected to operate continuously.
(b) Individual systems which have a design airflow rate or 3000 cfm or less.
(c) Gravity and other non-electrical ventilation systems controlled by readily accessible, manual damper controls.
(d) Where restricted by health and life safety codes.
403.2.7.3 Zone Isolation systems that serve zones that can be expected to operate nonsimultaneously for more than 750 hours per year shall include isolation devices and controls to shut off or set back the supply of heating and cooling to each zone independently. Isolation is not required for zones expected to operate continuously or expected to be inoperative only when all other zones are inoperative. For buildings where occupancy patterns are not known at the time of system design, such as speculative buildings, the designer may predesignate isolation areas. The grouping of zones on one floor into a single isolation area shall be permitted when the total conditioned floor area does not exceed 25,000 ft2 per group.
403.2.8Economizer Controls.
403.2.8.1 Each fan system shall be designed and capable of being controlled to take advantage of favorable weather conditions to reduce mechanical cooling requirements. The system shall include either: A temperature or enthalpy air economizer system that is capable of automatically modulating outside air and return air dampers to provide up to 85% of the design supply air quantity as outside air, or a water economizer system that is capable of cooling supply air by direct and/or indirect evaporation and is capable of providing 100% of the expected system cooling load at outside air temperatures of 50 °F dry-bulb/45 °F wet-bulb and below. Exceptions are as follows:
(a) Individual fan-cooling units with a supply capacity of less than 3000 cfm or a total cooling capacity less than 90,000 Btu/h.
(b) Systems with air-cooled or evaporatively cooled condensers that include extensive filtering equipment provided in order to meet the requirements of RS-41 (incorporated by reference, see § 434.701 ).
(c) Systems with air-cooled or evaporatively cooled condensers where the design engineer certifies to the building official that use of outdoor air cooling affects the operation of other systems, such as humidification, dehumidification, and supermarket refrigeration systems, so as to increase overall energy usage.
(d) Systems that serve envelope-dominated spaces whose sensible cooling load at design conditions, excluding transmission and infiltration loads, is less than or equal to transmission and infiltration losses at an outdoor temperature of 60 °F.
(e) Systems serving residential spaces and hotel or motel rooms.
(f) Systems for which at least 75% of the annual energy used for mechanical cooling is provided from a site-recovered or site-solar energy source.
(g) The zone(s) served by the system each have operable openings (windows, doors, etc.) with an openable area greater than 5% of the conditioned floor area. This applies only to spaces open to and within 20 ft of the operable openings. Automatic controls shall be provided that lock out system mechanical cooling to these zones when outdoor air temperatures are less than 60 °F.
403.2.8.2 Economizer systems shall be capable of providing partial cooling even when additional mechanical cooling is required to meet the remainder of the cooling load. Exceptions are as follows:
(a) Direct-expansion systems may include controls to reduce the quantity of outdoor air as required to prevent coil frosting at the lowest step of compressor unloading. Individual direct-expansion units that have a cooling capacity of 180,000 Btu/h or less may use economizer controls that preclude economizer operation whenever mechanical cooling is required simultaneously.
(b) Systems in climates with less than 750 average operating hours per year between 8 a.m. and 4 p.m. when the ambient dry-bulb temperatures are between 55 °F and 69 °F inclusive.
403.2.8.3 System design and economizer controls shall be such that economizer operation does not increase the building heating energy use during normal operation.
403.2.9Distribution System Construction and Insulation.
403.2.9.1Piping Insulation. All HVAC system piping shall be thermally insulated in accordance with Table 403.2.9.1. Exceptions are as follows:
(a) Factory-installed piping within HVAC equipment tested and rated in accordance with subsection 403.1 .
(b) Piping that conveys fluids that have a design operating temperature range between 55 °F and 105 °F.
(c) Piping that conveys fluids that have not been heated or cooled through the use of fossil fuels or electricity.

Table 403.2.9.1-Minimum Pipe Insulation (in.) a

Insulation conductivityaNominal pipe diameter (in.)
Fluid Design Operating Temp. Range (F) Conductivity Range Btu in./(h ft2 F) Mean Temp. F [LESS THAN]1.0 1.0 to 1.25 1.5 to 3.0 4.0 to 6.0 8.0
Heating systems (Steam, Steam Condensate, and Hot Water)b c
[GREATER THAN]3500.32-0.342501.01.51.52.02.5
251-3500.29-0.322001.01.01.52.02.0
201-2500.27-0.301501.01.01.01.51.5
141-2000.25-0.291251.01.01.01.51.5
105-1400.22-0.281000.50.50.751.01.0
Domestic and Service Hot Water Systems
105 and Greater0.22-0.281000.50.50.751.01.0
Cooling Systems (Chilled Water, Brine, and Refrigerant)d
40-550.22-0.281000.50.50.50.50.5
Below 400.22-0.281000.50.50.50.50.5

a For insulation outside the stated conductivity range, the minimum thickness (T) shall be determined as follows: T = r{1 + t/r)K/k - 1}

Where T = minimum insulation thickness (in), r = actual outside radius of pipe (in), t = insulation thickness listed in this table for applicable fluid temperature and pipe size, K = conductivity of alternate material at mean rating temperature indicated for the applicable fluid temperature (Btu in/h ft2 F); and k = the upper value of the conductivity range listed in this table for the applicable fluid temperature.

b These thicknesses are based on energy efficiency considerations only. Safety issues, such as insulation surface temperatures, have not been considered.

c Piping insulation is not required between the control valve and coil on run-outs when the control valve is located within four feet of the coil and the pipe diameter is 1 inch or less.

d Note that the required minimum thickness does not take water vapor transmission and possible surface condensation into account.

Table 403.2.9.2-Minimum Duct Insulation R-value a

Duct locationCooling supply ductsHeating supply ductsReturn ducts
CDD65 [LESS THAN EQUAL TO]500500 [LESS THAN]CDD65 [LESS THAN EQUAL TO]1,0001,000 [LESS THAN]CDD65 [LESS THAN EQUAL TO]2,000CDD65 [GREATER THAN EQUAL TO]2,000HDD65 [LESS THAN EQUAL TO]1,5001,500 [LESS THAN]HDD65 [LESS THAN EQUAL TO]4,5004,500 [LESS THAN]HDD65 [LESS THAN EQUAL TO]7,500HDD65 [GREATER THAN EQUAL TO]7,500
Exterior of BuildingR-3.3R-5.0R-6.5R-8.0R-3.3R-5.0R-6.5R-8.0R-5.0
Ventilated AtticR-3.3R-3.3R-3.3R-5.0R-5.0R-5.0R-5.0R-5.0R-3.3
Unvented AtticR-5.0R-5.0R-5.0R-5.0R-5.0R-5.0R-5.0R-5.0R-3.3
Other Conditioned SpacesbR-3.3R-3.3R-3.3R-3.3R-3.3R-3.3R-3.3R-3.3R-3.3
Indirectly Conditioned SpacescnoneR-3.3R-3.3R-3.3R-3.3R-3.3R-3.3R-3.3none
BuriednonenonenonenoneR-5.0R-5.0R-5.0R-5.0R-3.3

a Insulation R-values, measured in (h.ft2.°F)/Btu, are for the insulation as installed and do not include film resistance. The required minimum thickness do not consider water vapor transmission and possible surface condensation. The required minimum thicknesses do not consider water vapor transmission and condensation. For ducts that are designed to convey both heated and cooled air, duct insulation shall be as required by the most restrictive condition. Where exterior walls are used as plenum walls, wall insulation shall be as required by the most restrictive condition of this section or subsection 402. Insulation resistance measured on a horizontal plane in accordance with RS-6 (incorporated by reference, see § 434.701 ) at a mean temperature of 75 °F. RS-6 is in incorporated by reference at § 434.701 .

b Includes crawl spaces, both ventilated and non-ventilated.

c Includes return air plenums, with and without exposed roofs above.

403.2.9.2Duct and Plenum Insulation. All supply and return air ducts and plenums installed as part of an HVAC air distribution system shall be thermally insulated in accordance with Table 403.2.9.1. Exceptions are as follows:
(a) Factory-installed plenums, casings, or ductwork furnished as a part of the HVAC equipment tested and rated in accordance with subsection 403.1
(b) Ducts within the conditioned space that they serve. (incorporated by reference, see § 434.701 ) ca a06oc0.186
403.2.9.3Duct and Plenum Construction. All air-handling ductwork and plenums shall be constructed and erected in accordance with RS-34, RS-35, and RS-36 (incorporated by reference, see § 434.701 ). Where supply ductwork and plenums designed to operate at static pressures from 0.25 in. wc to 2 in. wc, inclusive, are located outside of the conditioned space or in return plenums, joints shall be sealed in accordance with Seal Class C as defined in RS-34 (incorporated by reference, see § 434.701 ). Pressure sensitive tape shall not be used as the primary sealant where such ducts are designed to operate at static pressures of 1 in. wc, or greater.
403.2.9.3.1 Ductwork designed to operate at static pressures in excess of 3 in. wc shall be leak-tested in accordance with Section 5 of RS-35, (incorporated by reference, see § 434.701 ), or equivalent. Test reports shall be provided in accordance with Section 6 of RS-35, (incorporated by reference, see § 434.701 ) m or equivalent. The tested duct leakage class at a test pressure equal to the design duct pressure class rating shall be equal to or less than leakage Class 6 as defined in Section 4.1 of RS-35 (incorporated by reference, see § 434.701 ). Representative sections totaling at least 25% of the total installed duct area for the designated pressure class shall be tested.
403.2.10Completion.
403.2.10.1Manuals. Construction documents shall require an operating and maintenance manual provided to the Federal Agency. The manual shall include, at a minimum, the following:
(a) Submittal data stating equipment size and selected options for each piece of equipment requiring maintenance, including assumptions used in outdoor design calculations.
(b) Operating and maintenance manuals for each piece of equipment requiring maintenance. Required maintenance activity shall be specified.
(c) Names and addresses of at least one qualified service agency to perform the required periodic maintenance shall be provided.
(d) HVAC controls systems maintenance and calibration information, including wiring diagrams, schematics, and control sequence descriptions. Desired or field determined setpoints shall be permanently recorded on control drawings, at control devices, or, for digital control systems, in programming comments.
(e) A complete narrative, prepared by the designer, of how each system is intended to operate shall be included with the construction documents.
403.2.10.2Drawings. Construction documents shall require that within 30 days after the date of system acceptance, record drawings of the actual installation be provided to the Federal agency. The drawings shall include details of the air barrier installation in every envelope component, demonstrating continuity of the air barrier at all joints and penetrations.
403.2.10.3Air System Balancing. Construction documents shall require that all HVAC systems be balanced in accordance with the industry accepted procedures (such as National Environmental Balancing Bureau (NEBB) Procedural Standards, Associated Air Balance Council (AABC) National Standards, or ANSI/ASHRAE Standard 111). Air and water flow rates shall be measured and adjusted to deliver final flow rates within 10% of design rates, except variable flow distribution systems need not be balanced upstream of the controlling device (VAV box or control valve).
403.2.10.3.1 Construction documents shall require a written balance report be provided to the Federal agency for HVAC systems serving zones with a total conditioned area exceeding 5,000 ft2.
403.2.10.3.2 Air systems shall be balanced in a manner to first minimize throttling losses, then fan speed shall be adjusted to meet design flow conditions or equivalent procedures. Exceptions are as follows: Damper throttling may be used for air system balancing;
(a) With fan motors of 1 hp (0.746 kW) or less, or
(b) Of throttling results in no greater than 1/3 hp (0.248 kW) fan horsepower draw above that required if the fan speed were adjusted.
403.2.10.4Hydronic System Balancing. Hydronic systems shall be balanced in a manner to first minimize throttling losses; then the pump impeller shall be trimmed or pump speed shall be adjusted to meet design flow conditions. Exceptions are as follows:
(a) Pumps with pump motors of 10 hp (7.46 kW) or less.
(b) If throttling results in no greater than 3 hp (2.23 kW) pump horsepower draw above that required if the impeller were trimmed.
(c) To reserve additional pump pressure capability in open circuit piping systems subject to fouling. Valve throttling pressure drop shall not exceed that expected for future fouling.
403.2.10.5Control System Testing. HVAC control systems shall be tested to assure that control elements are calibrated, adjusted, and in proper working condition. For projects larger than 50,000 ft2 conditioned area, detailed instructions for commissioning HVAC systems shall be provided by the designer in plans and specifications.

10 C.F.R. §434.403