10 C.F.R. § 434.402

Current through November 30, 2024
Section 434.402 - Building envelope assemblies and materials

The building envelope and its associated assemblies and materials shall meet the provisions of this section.

402.1Calculations and Supporting Information.
402.1.1Material Properties. Information on thermal properties, building envelope system performance, and component heat transfer shall be obtained from RS-4. When the information is not available from RS-4, (incorporated by reference, see § 434.701 ) the data shall be obtained from manufacturer's information or laboratory or field test measurements using RS-5, RS-6, RS-7, or RS-8 (incorporated by reference, see § 434.701 ).
402.1.1.1 The shading coefficient (SC) for fenestration shall be obtained from RS-4 (incorporated by reference, see § 434.701 ) or from manufacturer's test data. The shading coefficient of the fenestration, including both internal and external shading devices, is SCX and excludes the effect of external shading projections, which are calculated separately. The shading coefficient used for louvered shade screens shall be determined using a profile angle of 30 degrees as found in Table 41, Chapter 27 of RS-4 (incorporated by reference, see § 434.701 ).
402.1.2Thermal Performance Calculations. The overall thermal transmittance of the building envelope shall be calculated in accordance with Equation 402.1.2:

View Image

Where:

Uo = the area-weighted average thermal transmittance of the gross area of the building envelope; i.e., the exterior wall assembly including fenestration and doors, the roof and ceiling assembly, and the floor assembly, Btu/(h·ft2·°F)

Ao = the gross area of the building envelope, ft2

Ui = the thermal transmittance of each individual path of the building envelope, i.e., the opaque portion or the fenestration, Btu/(h·ft2·°F)

Ui = 1/Ri (where Ri is the total resistance to heat flow of an individual path through the building envelope)

Ai = the area of each individual element of the building envelope, ft2

The thermal transmittance of each component of the building envelope shall be determined with due consideration of all major series and parallel heat flow paths through the elements of the component and film coefficients and shall account for any compression of insulation. The thermal transmittance of opaque elements of assemblies shall be determined using a series path procedure with corrections for the presence of parallel paths within an element of the envelope assembly (such as wall cavities with parallel paths through insulation and studs). The thermal performance of adjacent ground in below-grade applications shall be excluded from all thermal calculations.

402.1.2.1 Envelope Assemblies Containing Metal Framing. The thermal transmittance of the envelope assembly containing metal framing shall be determined from one of three methods:
(a) Laboratory or field test measurements based on RS-5, RS-6, RS-7, or RS-8 (incorporated by reference, see § 434.701 ).
(b) The zone method described in Chapter 22 of RS-4 (incorporated by reference, see § 434.701 ) and the formulas on page 22.10.
(c) For metal roof trusses or metal studs covered by Tables 402.1.2.1a and b, the total resistance of the series path shall be calculated in accordance with the following Equations:

View Image

Where:

Rt = the total resistance of the envelope assembly

Ri = the resistance of the series elements (for i = 1 to n) excluding the parallel path element(s)

Re = the equivalent resistance of the element containing the parallel path (R-value of insulation * Fc). Values for Fc and equivalent resistances shall be taken from Tables 402.1.2.1a or b.

Table 402.1.2.1a-Parallel Path Correction Factors-Metal Roof Trusses Spaced 4 ft. o.c. or Greater That Penetrate the Insulation

Effective framing cavity R-values Correction
factor
Fc
Equivalent
resistance
Re1
R-01.00R-0
R-50.96R-4.8
R-100.92R-9.2
R-150.88R-13.2
R-200.85R-17.0
R-250.81R-20.3
R-300.79R-23.7
R-350.76R-26.6
R-400.73R-29.2
R-450.71R-32.0
R-500.69R-34.5
R-550.67R-36.0

1 Based on 0.66-inch-diameter cross members every one foot.

Table 402.1.2.1b-Parallel Path Correction Factors-Metal Framed Walls With Studs 16 Ga. or Lighter

Size of members Spacing of
framing, in.
Cavity
insulation R-Value
Correction
factor
Fc
Equivalent
resistance
Re
2 * 416 O.C.R-11
R-13
R-15
0.50
0.46
0.43
R-5.5
R-6.0
R-6.4
2 * 424 O.C.R-11
R-13
R-15
0.60
0.55
0.52
R-6.6
R-7.2
R-7.8
2 * 616 O.C.R-19
R-21
0.37
0.35
R-7.1
R-7.4
2 * 624 O.C.R-19
R-21
0.45
0.43
R-8.6
R-9.0
2 * 816 O.C.R-250.31R-7.8
2 * 824 O.C.R-250.38R-9.6

402.1.2.2Envelope Assemblies Containing Nonmetal Framing. The thermal transmittance of the envelope assembly shall be determined from laboratory or field test measurements based on RS-5, RS-6, RS-7, or RS-8 (incorporated by reference, see § 434.701 ) or from the series-parallel (isothermal planes) method provided in page 23.2 of Chapter 23 of RS-4 (incorporated by reference, see § 434.701 ).
402.1.2.3Metal Buildings. For elements with internal metallic structures bonded on one or both sides to a metal skin or covering, the calculation procedure specified in RS-9 (incorporated by reference, see § 434.701 ) shall be used.
402.1.2.4Fenestration Assemblies. Determine the overall thermal transmittance of fenestration assemblies in accordance with RS-18 and RS-19 (incorporated by reference, see § 434.701 ) or by calculation. Calculation of the overall thermal transmittance of fenestration assemblies shall consider the center-of-glass, edge-of-glass, and frame components.
(a) The following equation 402.1.2.4a shall be used.

View Image

Where:

Uof = the overall thermal transmittance of the fenestration assemblies, including the center-of-glass, edge-of-glass, and frame components, Btu/(h·ft2·°F)

i = numerical subscript (1, 2, . . .n) refers to each of the various fenestration types present in the wall

n = the number of fenestration assemblies in the wall assembly

Ucg = the thermal transmittance of the center-of-glass area, Btu/(h·ft2·°F)

Acg = the center of glass area, that is the overall visible glass area minus the edge-of-glass area, ft2

Ueg = the thermal transmittance of the edge of the visible glass area including the effects of spacers in multiple glazed units, Btu/(h·ft2·°F)

Aeg = the edge of the visible glass area, that is the 2.5 in. perimeter band adjacent to the frame, ft2

Uf = the thermal transmittance of the frame area, Btu/(h·ft2·°F)

Af = the frame area that is the overall area of the entire glazing product minus the center-of-glass area and minus the edge-of-glass area, ft2

(b) Values of Uof shall be based on one of the following methods:
(1) Results from laboratory test of center-of-glass, edge-of-glass, and frame assemblies tested as a unit at winter conditions. One of the procedures in Section 8.3.2 of RS-1 (incorporated by reference, see § 434.701 ) shall be used.
(2) Overall generic product C (commercial) in Table 13, Chapter 27, of the RS-4 (incorporated by reference, see § 434.701 ). The generic product C in Table 13, Chapter 27, is based on a product of 24 ft2. Larger units will produce lower U-values and thus it is recommended to use the calculation procedure detailed in Equation 402.1.2.4a.
(3) Calculations based on the actual area for center-of-glass, edge-of-glass, and frame assemblies and on the thermal transmittance of components derived from 402.1.2.4a, 402.1.2.4b or a combination of the two.
402.1.3Gross Areas of Envelope Components.
402.1.3.1Roof Assembly. The gross area of a roof assembly shall consist of the total surface of the roof assembly exposed to outside air or unconditioned spaces and is measured from the exterior faces of exterior walls and centerline of walls separating buildings. The roof assembly includes all roof or ceiling components through which heat may flow between indoor and outdoor environments, including skylight surfaces but excluding service openings. For thermal transmittance purposes when return air ceiling plenums are employed, the roof or ceiling assembly shall not include the resistance of the ceiling or the plenum space as part of the total resistance of the assembly.
402.1.3.2Floor Assembly. The gross area of a floor assembly over outside or unconditioned spaces shall consist of the total surface of the floor assembly exposed to outside air or unconditioned space and is measured from the exterior face of exterior walls and centerline of walls separating buildings. The floor assembly shall include all floor components through which heat may flow between indoor and outdoor or unconditioned space environments.
402.1.3.3Wall Assembly. The gross area of exterior walls enclosing a heated or cooled space is measured on the exterior and consists of the opaque walls, including between-floor spandrels, peripheral edges of flooring, window areas (including sash), and door areas but excluding vents, grilles, and pipes.
402.2Air Leakage and Moisture Mitigation. The requirements of this section shall apply only to those building components that separate interior building conditioned space from the outdoors or from unconditioned space or crawl spaces. Compliance with the criteria for air leakage through building components shall be determined by tests conducted in accordance with RS-10 (incorporated by reference, see § 434.701 ).
402.2.1Air Barrier System. A barrier against leakage shall be installed to prevent the leakage of air through the building envelope according to the following requirements:
(a) The air barrier shall be continuous at all plumbing and heating penetrations of the building opaque wall.
(b) The air barrier shall be sealed at all penetrations of the opaque building wall for electrical and telecommunications equipment.

Table 402.2.1-Air Leakage for Fenestration and Doors Maximum Allowable Infiltration Rate

Component Reference
standard
cfm/lin ft Sash
crack or cfm/ft2
of area
Fenestration
Aluminum:
OperableRS-11*0.37 cfm/lin ft.
JalousieRS-11*1.50 cfm/ft2.
FixedRS-11*0.15 cfm/ft2.
Poly Vinyl Chloride (PVC):
Prime WindowsRS-12*0.37 cfm/ft2.
Wood:
ResidentialRS-13*0.37 cfm/ft2.
Light CommercialRS-13*0.25 cfm/ft2.
Heavy CommercialRS-13*0.15 cfm/ft2.
Sliding Glass Doors:
AluminumRS-11*0.37 cfm/ft2.
PVCRS-12*0.37 cfm/lin ft.
Doors-Wood:
ResidentialRS-14*0.34 cfm/ft2.
Light CommercialRS-14*0.25 cfm/ft2.
Heavy CommercialRS-14*0.10 cfm/ft2.
Commercial Entrance DoorsRS-10*1.25 cfm/ft2.
Residential Swinging DoorsRS-10*0.50 cfm/ft2.
Wall Sections AluminumRS-10*0.06 cfm/ft2.

NOTE: [The "Maximum Allowable Infiltration Rates" are from current standards to allow the use of available products.]

* Incorporated by reference, see § 434.701 .

402.2.2Building Envelope. The following areas of the building envelope shall be sealed, caulked, gasketed, or weatherstripped to limit air leakage:
(a) Intersections of the fenestration and door frames with the opaque wall sections.
(b) Openings between walls and foundations, between walls and roof and wall panels.
(c) Openings at penetrations of utility service through, roofs, walls, and floors.
(d) Site built fenestration and doors.
(e) All other openings in the building envelope.

Exceptions are as follows: Outside air intakes, exhaust outlets, relief outlets, stair shaft, elevator shaft smoke relief openings, and other similar elements shall comply with subsection 403.

402.2.2.1 Fenestration and Doors Fenestration and doors shall meet the requirements of Table 402.2.1.
402.2.2.2Building Assemblies Used as Ducts or Plenums. Building assemblies used as ducts or plenums shall be sealed, caulked, and gasketed to limit air leakage.
402.2.2.3Vestibules. A door that separates conditioned space from the exterior shall be equipped with an enclosed vestibule with all doors opening into and out of the vestibule equipped with self-closing devices. Vestibules shall be designed so that in passing through the vestibule, it is not necessary for the interior and exterior doors to open at the same time. Exceptions are as follows: Exterior doors need not be protected with a vestibule where:
(a) The door is a revolving door.
(b) The door is used primarily to facilitate vehicular movement or material handling.
(c) The door is not intended to be used as a general entrance door.
(d) The door opens directly from a dwelling unit.
(e) The door opens directly from a retail space less than 2,000 ft2 in area, or from a space less than 1,500 ft2 for other uses.
(f) In buildings less than three stories in building height in regions that have less than 6,300 heating degree days base 65 °F.
402.2.2.4Compliance Testing. All buildings shall be tested after completion using the methodology in RS-11, (incorporated by reference, see § 434.701 ) or an equivalent approved method to determine the envelope air leakage. A standard blower door test is an acceptable technique to pressurize the building if the building is 5,000 ft2 or less in area. The building's air handling system can be used to pressurize the building if the building is larger than 5,000 ft2. The following test conditions shall be:
(a) The measured envelope air leakage shall not exceed 1.57 pounds per square foot of wall area at a pressure difference of 0.3 inches water.
(b) At the time of testing, all windows and outside doors shall be installed and closed, all interior doors shall be open, and all air handlers and dampers shall be operable. The building shall be unoccupied.
(c) During the testing period, the average wind speed during the test shall be less than 6.6 feet per second, the average outside temperature greater than 59 °F, and the average inside-outside temperature difference is less than 41 °F.
402.2.2.5Moisture Migration. The building envelope shall be designed to limit moisture migration that leads to deterioration in insulation or equipment performance as determined by the following construction practices:
(a) A vapor retarder shall be installed to retard, or slow down the rate of water vapor diffusion through the building envelope. The position of the vapor retarder shall be determined taking into account local climate and indoor humidity levels. The methodologies presented in Chapter 20 of RS-4 (incorporated by reference, see § 434.701 ) shall be used to determine temperature and water vapor profiles through the envelope systems to assess the potential for condensation within the envelope and to determine the position of the vapor retarder within the envelope system.
(b) The vapor retarder shall be installed over the entire building envelope.
(c) The perm rating requirements of the vapor retarder shall be determined using the methodologies contained in Chapter 20 of RS-4, (incorporated by reference, see § 434.701 ) and shall take into account local climate and indoor humidity level. The vapor retarder shall have a performance rating of 1 perm or less.
402.3Thermal Performance Criteria.
402.3.1Roofs; Floors and Walls Adjacent to Unconditioned Spaces. The area weighted average thermal transmittance of roofs and also of floors and walls adjacent to unconditioned spaces shall not exceed the criteria in Table 402.3.1a. Exceptions are as follows: Skylights for which daylight credit is taken may be excluded from the calculations of the roof assembly Uor if all of the following conditions are met:
(a) The opaque roof thermal transmittance is less than the criteria in Table 402.3.1b.
(b) Skylight areas, including framing, as a percentage of the roof area do not exceed the values specified in Table 402.3.1b. The maximum skylight area from Table 402.3.1b may be increased by 50% if a shading device is used that blocks over 50% of the solar gain during the peak cooling design condition. For shell buildings, the permitted skylight area shall be based on a light level of 30 foot candles and a lighting power density (LPD) of less than 1.0 w/ft2. For speculative buildings, the permitted skylight area shall be based on the unit lighting power allowance from Table 401.3.2a and an illuminance level as follows: for LPD [LESS THAN]1.0, use 30 footcandles; for 1.0 [LESS THAN]LPD [LESS THAN]2.5, use 50 footcandles; and for LPD [GREATER THAN EQUAL TO]2.5, use 70 footcandles.
(c) All electric lighting fixtures within daylighted zones under skylights are controlled by automatic daylighting controls.
(d) The Uo of the skylight assembly including framing does not exceed____________Btu/(h·ft2·°F) [Use 0.70 for [LESS THAN EQUAL TO]8000 HDD65 and 0.45 for [GREATER THAN]8000 HDD65 or both if the jurisdiction includes cities that are both below and above 8000 HDD65.]
(e) Skylight curb U-value does not exceed 0.21 Btu/(h·ft2·°F).
(f) The infiltration coefficient of the skylights does not exceed 0.05 cfm/ft2.
402.3.2Below-Grade Walls and Slabs-on-Grade. The thermal resistance (R-value) of insulation for slabs-on-grade, or the overall thermal resistance of walls in contact with the earth, shall be equal to or greater than the values in Table 402.3.2.
402.4Exterior Walls. Exterior walls shall comply with either 402.4.1 or 402.4.2.
402.4.1Prescriptive Criteria. (a) The exterior wall shall be designed in accordance with subsections 402.4.1.1 and 402.4.1.2 . When the internal load density range is not known, the 0-1.50 W/ft2 range shall be used for residential, hotel/motel guest rooms, or warehouse occupancies; the 3.01-3.50 w/ft2 range shall be used for retail stores smaller than 2,000 ft2 and technical and vocational schools smaller than 10,000 ft2; and the 1.51-3.00 W/ft2 range shall be used for all other occupancies and building sizes. When the building envelope is designed or constructed prior to knowing the building occupancy type, an internal load density of ______ W/ft2 shall be used. [Use 3.0 W/ft2 for HDD65 [LESS THAN]3000, 2.25 W/ft2 for 3000 [LESS THAN]HDD65 [LESS THAN]6000, and 1.5 W/ft2 for HDD65 [GREATER THAN]6000.]

(b) When more than one condition exists, area weighted averages shall be used. This requirement shall apply to all thermal transmittances, shading coefficients, projection factors, and internal load densities rounded to the same number of decimal places as shown in the respective table.

402.4.1.1 Opaque Walls. The weighted average thermal transmittance (U-value) of opaque wall elements shall be less than the values in Table 402.4.1.1. For mass walls (HC [GREATER THAN EQUAL TO]5), criteria are presented for low and high window/wall ratios and the criteria shall be determined by interpolating between these values for the window/wall ratio of the building.

402.4.1.2 Fenestration. The design of the fenestration shall meet the criteria of Table 402.4.1.2. When the fenestration columns labeled "Perimeter Daylighting" are used, automatic daylighting controls shall be installed in the perimeter daylighted zones of the building. These daylighting controls shall be capable of reducing electric lighting power to at least 50% of full power. Only those shading or lighting controls for perimeter daylighting that are shown on the plans shall be considered. The column labeled "VLT [GREATER THAN]= SC" shall be used only when the shading coefficient of the glass is less than its visible light transmittance.

Appendix A

The example Alternate Component Package tables illustrate the requirements of subsections 434.301.1 , 434.402.3.1 , 434.402.3.2 , 434.402.4.1.1 and 434.402.4.1.2 . Copies of specific tables contained in this appendix A can be obtained from the Energy Code for Federal Commercial Buildings, Docket No. EE-RM-79-112-C, EE-43, Office of Building Research and Standards, U.S. Department of Energy, Room 1J-018, 1000 Independence Avenue, SW., Washington, DC 20585, (202) 586-9127.

View Image

402.4.2System Performance Criteria. The cumulative annual energy flux attributable to thermal transmittance and solar gains shall be less than the criteria determined using the ENVSTD24 computer program in Standard 90.1-1989, or the equations in RS-1, (incorporated by reference, see § 434.701 ) Attachment 8-B. The cumulative annual energy flux shall be calculated using the ENVSTD24 computer program or the equations in RS-1, (incorporated by reference, see § 434.701 ) Attachment 8-B.

Table 402.4.2-EQUIP Default Values for ENVSTD24

Occupancy Default equipment power density1 Default occupant load adjustment1 Default adjusted equipment power density
Assembly0.250.751.00
Health/Institutional1.00-0.260.74
Hotel/Motel0.25-0.330.00
Warehouse/Storage0.10-0.600.00
Multi-Family High Rise0.75N/A0.00
Office0.75-0.350.40
Restaurant0.100.070.17
Retail0.25-0.380.00
School0.500.300.80

1 Defaults as defined in Section 8.6.10.5 , Table 8-4, and Sections 8.6.10.6 and 13.7.2.1 , Table 13-2 from RS-1 (incorporated by reference, see § 434.701 ).

402.4.2.1Equipment Power Density (EQUIP). The equipment power density used in the ENVSTD24 computer program shall use the actual equipment power density from the building plans and specifications or be taken from Table 402.4.2 using the column titled "Default Adjusted Equipment Power Density" or calculated for the building using the procedures of RS-1. (incorporated by reference, see § 434.701 ). The program limits consideration of the equipment power density to a maximum of 1 W/ft2.
402.4.2.2Lighting Power Density (LIGHTS). The lighting power density used in the ENVSTD24 computer program shall use the actual lighting power density from the building plans and specifications or the appropriate value from Tables 401.3.2a, b, c, or d.
402.4.2.3Daylighting Control Credit Fraction (DLCF). When the daylighting control credit fraction is other than zero, automatic daylighting controls shall be installed in the appropriate perimeter zones(s) of the building to justify the credit.

10 C.F.R. §434.402