10 C.F.R. § 429.16

Current through October 31, 2024
Section 429.16 - [Effective until 12/23/2024] Central air conditioners and central air conditioning heat pumps
(a)Determination of Represented Value -
(1)Required represented values. Determine the represented values (including SEER, EER, HSPF, SEER2, EER2, HSPF2, PW,OFF, cooling capacity, and heating capacity, as applicable) for the individual models/combinations (or "tested combinations") specified in the following table.

Table 1 to Paragraph (a)(1)

Category Equipment subcategory Required represented values
Single-Package UnitSingle-Package Air Conditioner (AC) (including space-constrained)Every individual model distributed in commerce.
Single-Package Heat Pump (HP) (including space-constrained)
Outdoor Unit and Indoor Unit (Distributed in Commerce by Outdoor Unit Manufacturer (OUM))Single-Split-System AC with Single-Stage or Two-Stage Compressor (including Space-Constrained and Small-Duct, High Velocity Systems (SDHV))Every individual combination distributed in commerce. Each model of outdoor unit must include a represented value for at least one coil-only individual combination that is distributed in commerce and which is representative of the least efficient combination distributed in commerce with that particular model of outdoor unit. For that particular model of outdoor unit, additional represented values for coil-only and blower-coil individual combinations are allowed, if distributed in commerce.
Single-Split System AC with Other Than Single-Stage or Two-Stage Compressor (including Space-Constrained and SDHV)Every individual combination distributed in commerce, including all coil-only and blower-coil combinations.
Single-Split-System HP (including Space-Constrained and SDHV)Every individual combination distributed in commerce.
Multi-Split, Multi-Circuit, or Multi-Head Mini-Split Split System-non-SDHV (including Space-Constrained)For each model of outdoor unit, at a minimum, a non-ducted "tested combination." For any model of outdoor unit also sold with models of ducted indoor units, a ducted "tested combination." When determining represented values on or after January 1, 2023, the ducted "tested combination" must comprise the highest static variety of ducted indoor unit distributed in commerce (i.e., conventional, mid-static, or low-static). Additional representations are allowed, as described in paragraphs (c)(3)(i) and (ii) of this section, respectively.
Multi-Split, Multi-Circuit, or Multi-Head Mini-Split Split System-SDHVFor each model of outdoor unit, an SDHV "tested combination." Additional representations are allowed, as described in paragraph (c)(3)(iii) of this section.
Indoor Unit Only Distributed in Commerce by Independent Coil Manufacturer (ICM)Single-Split-System Air Conditioner (including Space-Constrained and SDHV)
Single-Split-System Heat Pump (including Space-Constrained and SDHV)
Every individual combination distributed in commerce.
Multi-Split, Multi-Circuit, or Multi-Head Mini-Split Split System-SDHVFor a model of indoor unit within each basic model, an SDHV "tested combination." Additional representations are allowed, as described in paragraph (c)(3)(iii) of this section.
Outdoor Unit with no MatchEvery model of outdoor unit distributed in commerce (tested with a model of coil-only indoor unit as specified in paragraph (b)(2)(i) of this section).

(2)PW,OFF. If individual models of single-package systems or individual combinations (or "tested combinations") of split systems that are otherwise identical are offered with multiple options for off mode-related components, determine the represented value for the individual model/combination with the crankcase heater and controls that are the most consumptive. A manufacturer may also determine represented values for individual models/combinations with less consumptive off mode options; however, all such options must be identified with different model numbers for single-package systems or for outdoor units (in the case of split systems).
(3)Refrigerants.
(i) If a model of outdoor unit (used in a single-split, multi-split, multi-circuit, multi-head mini-split, and/or outdoor unit with no match system) is distributed in commerce and approved for use with multiple refrigerants, a manufacturer must determine all represented values for that model using each refrigerant that can be used in an individual combination of the basic model (including outdoor units with no match or "tested combinations"). This requirement may apply across the listed categories in the table in paragraph (a)(1) of this section. A refrigerant is considered approved for use if it is listed on the nameplate of the outdoor unit. If any of the refrigerants approved for use is HCFC-22 or has a 95 °F midpoint saturation absolute pressure that is ± 18 percent of the 95 °F saturation absolute pressure for HCFC-22, or if there are no refrigerants designated as approved for use, a manufacturer must determine represented values (including SEER, EER, HSPF, SEER2, EER2, HSPF2, PW,OFF, cooling capacity, and heating capacity, as applicable) for, at a minimum, an outdoor unit with no match. If a model of outdoor unit is not charged with a specified refrigerant from the point of manufacture or if the unit is shipped requiring the addition of more than two pounds of refrigerant to meet the charge required for testing per section 2.2.5 of appendix M or appendix M1 (unless either (a) the factory charge is equal to or greater than 70% of the outdoor unit internal volume times the liquid density of refrigerant at 95 °F or (b) an A2L refrigerant is approved for use and listed in the certification report), a manufacturer must determine represented values (including SEER, EER, HSPF, SEER2, EER2, HSPF2, PW,OFF, cooling capacity, and heating capacity, as applicable) for, at a minimum, an outdoor unit with no match.
(ii) If a model is approved for use with multiple refrigerants, a manufacturer may make multiple separate representations for the performance of that model (all within the same individual combination or outdoor unit with no match) using the multiple approved refrigerants. In the alternative, manufacturers may certify the model (all within the same individual combination or outdoor unit with no match) with a single representation, provided that the represented value is no more efficient than its performance using the least-efficient refrigerant. If a manufacturer certifies a single model with multiple representations for the different approved refrigerants, it may use an AEDM to determine the represented values for all other refrigerants besides the refrigerant used for testing. A single representation made for multiple refrigerants may not include equipment in multiple categories or equipment subcategories listed in the table in paragraph (a)(1) of this section.
(4)Limitations for represented values of individual combinations. The following paragraphs explains the limitations for represented values of individual combinations (or "tested combinations").
(i)Regional. A basic model (model of outdoor unit) may only be certified as compliant with a regional standard if all individual combinations within that basic model meet the regional standard for which it is certified, including the coil-only combination as specified in paragraph (a)(1) of this section, as applicable. A model of outdoor unit that is certified below a regional standard can only be rated and certified as compliant with a regional standard if the model of outdoor unit has a unique model number and has been certified as a different basic model for distribution in each region, where the basic model(s) certified as compliant with a regional standard meet the requirements of the first sentence. An ICM cannot certify an individual combination with a rating that is compliant with a regional standard if the individual combination includes a model of outdoor unit that the OUM has certified with a rating that is not compliant with a regional standard. Conversely, an ICM cannot certify an individual combination with a rating that is not compliant with a regional standard if the individual combination includes a model of outdoor unit that an OUM has certified with a rating that is compliant with a regional standard.
(ii)Multiple product classes. Models of outdoor units that are rated and distributed in individual combinations that span multiple product classes must be tested, rated, and certified pursuant to paragraph (a) of this section as compliant with the applicable standard for each product class. This includes multi-split systems, multi-circuit systems, and multi-head mini-split systems with a represented value for a mixed combination including both SDHV and either non-ducted or ducted indoor units.
(5)Requirements. All represented values under paragraph (a) of this section must be based on testing in accordance with the requirements in paragraph (b) of this section or the application of an AEDM or other methodology as allowed in paragraph (c) of this section.
(b)Units tested -
(1)General. The general requirements of § 429.11 apply to central air conditioners and heat pumps; and
(2)Individual model/combination selection for testing.
(i) The table identifies the minimum testing requirements for each basic model that includes multiple individual models/combinations; if a basic model spans multiple categories or subcategories listed in the table, multiple testing requirements apply. For each basic model that includes only one individual model/combination, test that individual model/combination. For single-split-system non-space-constrained air conditioners and heat pumps, when testing is required in accordance with 10 CFR part 430, subpart B, appendix M1, these requirements do not apply until July 1, 2024, provided that the manufacturer is certifying compliance of all basic models using an AEDM in accordance with paragraph (c)(1)(i)(B) of this section and paragraph (e)(2)(i)(A) of § 429.70 .

Table 2 to Paragraph (b)(2)(i)

Category Equipment subcategoryMust test: With:
Single-Package UnitSingle-Package AC (including Space-Constrained)
Single-Package HP (including Space-Constrained)
The individual model with the lowest seasonal energy efficiency ratio (SEER) (when testing in accordance with appendix M to subpart B of 10 CFR part 430) or SEER2 (when testing in accordance with appendix M1 to subpart B of 10 CFR part 430)N/A.
Outdoor Unit and Indoor Unit (Distributed in Commerce by OUM)Single-Split-System AC with Single-Stage or Two-Stage Compressor (including Space-Constrained and Small-Duct, High Velocity Systems (SDHV))The model of outdoor unitA model of coil-only indoor unit.
Single-Split-System HP with Single-Stage or Two-Stage Compressor (including Space-Constrained and SDHV)The model of outdoor unitA model of indoor unit.
Single-Split System AC or HP with Other Than Single-Stage or Two-Stage Compressor having a non-communicating coil-only individual combination (including Space-Constrained and SDHV)The model of outdoor unitA model of non-communicating coil-only indoor unit.
Single-Split System AC or HP with Other Than Single-Stage or Two-Stage Compressor without a non-communicating coil-only individual combination (including Space-Constrained and SDHV)The model of outdoor unitA model of indoor unit.
Multi-Split, Multi-Circuit, or Multi-Head Mini-Split Split System-non-SDHV (including Space-Constrained)The model of outdoor unitAt a minimum, a "tested combination" composed entirely of non-ducted indoor units. For any models of outdoor units also sold with models of ducted indoor units, test a second "tested combination" composed entirely of ducted indoor units (in addition to the non-ducted combination). If testing under appendix M1 to subpart B of 10 CFR part 430, the ducted "tested combination" must comprise the highest static variety of ducted indoor unit distributed in commerce (i.e., conventional, mid-static, or low-static).
Multi-Split, Multi-Circuit, or Multi-Head Mini-Split Split System-SDHVThe model of outdoor unitA "tested combination" composed entirely of SDHV indoor units.
Indoor Unit Only (Distributed in Commerce by ICM)Single-Split-System Air Conditioner (including Space-Constrained and SDHV)A model of indoor unitThe least efficient model of outdoor unit with which it will be paired where the least efficient model of outdoor unit is the model of outdoor unit in the lowest SEER combination (when testing under appendix M to subpart B of 10 CFR part 430) or SEER2 combination (when testing under appendix M1 to subpart B of 10 CFR part 430) as certified by the OUM. If there are multiple models of outdoor unit with the same lowest SEER (when testing under appendix M to subpart B of 10 CFR part 430) or SEER2 (when testing under appendix M1 to subpart B of 10 CFR part 430) represented value, the ICM may select one for testing purposes.
Single-Split-System Heat Pump (including Space-Constrained and SDHV)Nothing, as long as an equivalent air conditioner basic model has been tested If an equivalent air conditioner basic model has not been tested, must test a model of indoor unit
Multi-Split, Multi-Circuit, or Multi-Head Mini-Split Split System-SDHVA model of indoor unitA "tested combination" composed entirely of SDHV indoor units, where the outdoor unit is the least efficient model of outdoor unit with which the SDHV indoor unit will be paired. The least efficient model of outdoor unit is the model of outdoor unit in the lowest SEER combination (when testing under appendix M to subpart B of 10 CFR part 430) or SEER2 combination (when testing under appendix M1 to subpart B of 10 CFR part 430 ) as certified by the OUM. If there are multiple models of outdoor unit with the same lowest SEER represented value (when testing under appendix M to subpart B of 10 CFR part 430) or SEER2 represented value (when testing under appendix M1 to subpart B of 10 CFR part 430), the ICM may select one for testing purposes.
Outdoor Unit with No MatchThe model of outdoor unitA model of coil-only indoor unit meeting the requirements of section 2.2e of appendix M or M1 to subpart B of 10 CFR part 430 .

(ii) Each individual model/combination (or "tested combination") identified in paragraph (b)(2)(i) of this section is not required to be tested for PW,OFF. Instead, at a minimum, among individual models/combinations with similar off-mode construction (even spanning different models of outdoor units), a manufacturer must test at least one individual model/combination for PW,OFF.
(3)Sampling plans and represented values. For individual models (for single-package systems) or individual combinations (for split-systems, including "tested combinations" for multi-split, multi-circuit, and multi-head mini-split systems) with represented values determined through testing, each individual model/combination (or "tested combination") must have a sample of sufficient size tested in accordance with the applicable provisions of this subpart. For heat pumps (other than heating-only heat pumps), all units of the sample population must be tested in both the cooling and heating modes and the results used for determining all representations. The represented values for any individual model/combination must be assigned such that:
(i)Off-Mode. Any represented value of power consumption or other measure of energy consumption for which consumers would favor lower values must be greater than or equal to the higher of:
(A) The mean of the sample, where:

View Image

and,

x is the sample mean; n is the number of samples; and xi is the ith sample; Or,

(B) The upper 90 percent confidence limit (UCL) of the true mean divided by 1.05, where:

View Image

And

x is the sample mean; s is the sample standard deviation; n is the number of samples; and t0.90 is the t statistic for a 90 percent one-tailed confidence interval with n-1 degrees of freedom (from appendix D). Round represented values of off-mode power consumption to the nearest watt.

(ii)SEER, EER, HSPF, SEER2, EER2, and HSPF2. Any represented value of the energy efficiency or other measure of energy consumption for which consumers would favor higher values shall be less than or equal to the lower of:
(A) The mean of the sample, where:

View Image

and, x is the sample mean; n is the number of samples; and xi is the ith sample; or,

(B) The lower 90 percent confidence limit (LCL) of the true mean divided by 0.95, where:

View Image

And x is the sample mean; s is the sample standard deviation; n is the number of samples; and t0.90 is the t statistic for a 90 percent one-tailed confidence interval with n-1 degrees of freedom (from appendix D). Round represented values of EER, SEER, HSPF, EER2, SEER2, and HSPF2 to the nearest 0.05.

(iii)Cooling Capacity and Heating Capacity. The represented values of cooling capacity and heating capacity must each be a self-declared value that is:
(A) Less than or equal to the lower of:
(1) The mean of the sample, where:

View Image

and, x is the sample mean; n is the number of samples; and xi is the ith sample; or,

(2) The lower 90 percent confidence limit (LCL) of the true mean divided by 0.95, where:

View Image

And x is the sample mean; s is the sample standard deviation; n is the number of samples; and t0.90 is the t statistic for a 90 percent one-tailed confidence interval with n-1 degrees of freedom (from appendix D).

(B) Rounded according to:
(1) To the nearest 100 Btu/h if cooling capacity or heating capacity is less than 20,000 Btu/h,
(2) To the nearest 200 Btu/h if cooling capacity or heating capacity is greater than or equal to 20,000 Btu/h but less than 38,000 Btu/h, and
(3) To the nearest 500 Btu/h if cooling capacity or heating capacity is greater than or equal to 38,000 Btu/h and less than 65,000 Btu/h.
(c)Determination of represented values for all other individual models/combinations besides those specified in paragraph (b)(2) of this section -
(1)All basic models except outdoor units with no match and multi-split systems, multi-circuit systems, and multi-head mini-split systems.
(i) For every individual model/combination within a basic model other than the individual model/combination required to be tested pursuant to paragraph (b)(2) of this section, either-
(A) A sample of sufficient size, comprised of production units or representing production units, must be tested as complete systems with the resulting represented values for the individual model/combination obtained in accordance with paragraphs (b)(1) and (3) of this section; or
(B) The represented values of the measures of energy efficiency or energy consumption through the application of an AEDM in accordance with paragraph (d) of this section and § 429.70 . An AEDM may only be used to determine represented values for individual models or combinations in a basic model (or separate approved refrigerants within an individual combination) other than the individual model or combination(s) required for mandatory testing under paragraph (b)(2) of this section, except that, for single-split, non-space-constrained systems, when testing is required in accordance with 10 CFR part 430, subpart B, appendix M1, an AEDM may be used to rate the individual model or combination(s) required for mandatory testing under paragraph (b)(2) of this section until July 1, 2024, in accordance with paragraph (e)(2)(i)(A) of § 429.70 .
(ii) For every individual model/combination within a basic model tested pursuant to paragraph (b)(2) of this section, but for which PW,OFF testing was not conducted, the represented value of PW,OFF may be assigned through, either:
(A) The testing result from an individual model/combination of similar off-mode construction, or
(B) The application of an AEDM in accordance with paragraph (d) of this section and § 429.70 .
(2)Outdoor units with no match. All models of outdoor units with no match within a basic model must be tested. No model of outdoor unit with no match may be rated with an AEDM, other than to determine the represented values for models using approved refrigerants other than the one used in testing.
(3)For multi-split systems, multi-circuit systems, and multi-head mini-split systems. The following applies:
(i) When testing in accordance with 10 CFR part 430, subpart B, appendix M1, for basic models that include additional varieties of ducted indoor units (i.e., conventional, low-static, or mid-static) other than the one for which representation is required in paragraph (a)(1) of this section, if a manufacturer chooses to make a representation, the manufacturer must conduct testing of a tested combination according to the requirements in paragraph (b)(3) of this section.
(ii) When testing in accordance with 10 CFR part 430, subpart B, appendix M, for basic models composed of both non-ducted and ducted combinations, the represented value for the mixed non-ducted/ducted combination is the mean of the represented values for the non-ducted and ducted combinations as determined in accordance with paragraph (b)(3) of this section. When testing in accordance with 10 CFR part 430, subpart B, appendix M1, for basic models that include mixed combinations of indoor units (any two kinds of non-ducted, low-static, mid-static, and conventional ducted indoor units), the represented value for the mixed combination is the mean of the represented values for the individual component combinations as determined in accordance with paragraph (b)(3) of this section.
(iii) When testing in accordance with 10 CFR part 430, subpart B, appendix M, for basic models composed of both SDHV and non-ducted or ducted combinations, the represented value for the mixed SDHV/non-ducted or SDHV/ducted combination is the mean of the represented values for the SDHV, non-ducted, or ducted combinations, as applicable, as determined in accordance with paragraph (b)(3) of this section. When testing in accordance with 10 CFR part 430, subpart B, appendix M1, for basic models including mixed combinations of SDHV and another kind of indoor unit (any of non-ducted, low-static, mid-static, and conventional ducted), the represented value for the mixed SDHV/other combination is the mean of the represented values for the SDHV and other tested combination as determined in accordance with paragraph (b)(3) of this section.
(iv) All other individual combinations of models of indoor units for the same model of outdoor unit for which the manufacturer chooses to make representations must be rated as separate basic models, and the provisions of paragraphs (b)(1) through (3) and (c)(3)(i) through (iii) of this section apply.
(v) With respect to PW,OFF only, for every individual combination (or "tested combination") within a basic model tested pursuant to paragraph (b)(2) of this section, but for which PW,OFF testing was not conducted, the representative values of PW,OFF may be assigned through either:
(A) The testing result from an individual model or combination of similar off-mode construction, or
(B) Application of an AEDM in accordance with paragraph (d) of this section and § 429.70 .
(d)Alternative efficiency determination methods. In lieu of testing, represented values of efficiency or consumption may be determined through the application of an AEDM pursuant to the requirements of § 429.70(e) and the provisions of this section.
(1)Power or energy consumption. Any represented value of the average off mode power consumption or other measure of energy consumption of an individual model/combination for which consumers would favor lower values must be greater than or equal to the output of the AEDM but no greater than the standard.
(2)Energy efficiency. Any represented value of the SEER, EER, HSPF, SEER2, EER2, HSPF2 or other measure of energy efficiency of an individual model/combination for which consumers would favor higher values must be less than or equal to the output of the AEDM but no less than the standard.
(3)Cooling capacity. The represented value of cooling capacity of an individual model/combination must be no greater than the cooling capacity output simulated by the AEDM.
(4)Heating capacity. The represented value of heating capacity of an individual model/combination must be no greater than the heating capacity output simulated by the AEDM.
(e)Certification reports. This paragraph specifies the information that must be included in a certification report.
(1)General. The requirements of § 429.12 apply to central air conditioners and heat pumps.
(2)Public product-specific information. Pursuant to § 429.12(b)(13) , for each individual model (for single-package systems) or individual combination (for split-systems, including outdoor units with no match and "tested combinations" for multi-split, multi-circuit, and multi-head mini-split systems), a certification report must include the following public product-specific information: When certifying compliance with January 1, 2015, energy conservation standards, the seasonal energy efficiency ratio (SEER in British thermal units per Watt-hour (Btu/W-h)) or when certifying compliance with January 1, 2023, energy conservation standards, seasonal energy efficiency ratio 2 (SEER2 in British thermal units per Watt-hour (Btu/W-h)); the average off mode power consumption (PW,OFF in Watts); the cooling capacity in British thermal units per hour (Btu/h); the region(s) in which the basic model can be sold; when certifying compliance with January 1, 2023, energy conservation standards, the kind(s) of air conditioner or heat pump associated with the minimum external static pressure used in testing or rating (ceiling-mount, wall-mount, mobile home, low-static, mid-static, small duct high velocity, space-constrained, or conventional/not otherwise listed); and
(i) For heat pumps, when certifying compliance with January 1, 2015, energy conservation standards, the heating seasonal performance factor (HSPF in British thermal units per Watt-hour (Btu/W-h)) or, when certifying compliance with January 1, 2023, energy conservation standards, heating seasonal performance factor 2 (HSPF2 in British thermal units per Watt-hour (Btu/W-h));
(ii) For central air conditioners (excluding space-constrained products), when certifying compliance with January 1, 2015, energy conservation standards, the energy efficiency ratio (EER in British thermal units per Watt-hour (Btu/W-h)) from the A or A2 test, whichever applies, or when certifying compliance with January 1, 2023, energy conservation standards, the energy efficiency ratio 2 (EER2 in Btu/W-h);
(iii) For single-split-systems, whether the represented value is for a coil-only or blower coil system;
(iv) For multi-split, multiple-circuit, and multi-head mini-split systems (including VRF and SDHV), when certifying compliance with January 1, 2015, energy conservation standards, whether the represented value is for a non-ducted, ducted, mixed non-ducted/ducted system, SDHV, mixed non-ducted/SDHV system, or mixed ducted/SDHV system;
(v) For all split systems including outdoor units with no match, the refrigerant.
(3)Basic and individual model numbers. The basic model number and individual model number(s) required to be reported under § 429.12(b)(6) must consist of the following:

Equipment typeBasic model numberIndividual model number(s)
1 2 3
Single-Package (including Space-Constrained)Number unique to the basic modelPackageN/AN/A.
Single-Split System (including Space-Constrained and SDHV)Number unique to the basic modelOutdoor UnitIndoor UnitIf applicable-Air Mover (could be same as indoor unit if fan is part of indoor unit model number).
Multi-Split, Multi-Circuit, and Multi-Head Mini-Split System (including Space-Constrained and SDHV)Number unique to the basic modelOutdoor UnitWhen certifying a basic model based on tested combination(s): * * *
When certifying an individual combination: Indoor Unit(s)
If applicable-When certifying a basic model based on tested combination(s): * * *.
When certifying an individual combination: Air Mover(s).
Outdoor Unit with No MatchNumber unique to the basic modelOutdoor UnitN/AN/A.

(4)Additional product-specific information. Pursuant to § 429.12(b)(13) , for each individual model/combination (including outdoor units with no match and "tested combinations"), a certification report must include the following additional product-specific information: The cooling full load air volume rate for the system or for each indoor unit as applicable (in cubic feet per minute of standard air (scfm)); the air volume rates that represent normal operation for other test conditions including minimum cooling air volume rate, intermediate cooling air volume rate, full load heating air volume rate, minimum heating air volume rate, intermediate heating air volume rate, and nominal heating air volume rate (scfm) for the system or for each indoor unit as applicable, if different from the cooling full load air volume rate; whether the individual model uses a fixed orifice, thermostatic expansion valve, electronic expansion valve, or other type of metering device; the duration of the compressor break-in period, if used; whether the optional tests were conducted to determine the CDc value used to represent cooling mode cycling losses or whether the default value was used; the temperature at which the crankcase heater with controls is designed to turn on, if applicable; whether an inlet plenum was installed during testing; the duration of the indoor fan time delay, if used; and
(i) For heat pumps, whether the optional tests were conducted to determine the CDh value or whether the default value was used; and the maximum time between defrosts as allowed by the controls (in hours);
(ii) For multi-split, multiple-circuit, and multi-head mini-split systems, the number of indoor units tested with the outdoor unit; the nominal cooling capacity of each indoor unit and outdoor unit in the combination; and the indoor units that are not providing heating or cooling for part-load tests;
(iii) For ducted systems having multiple indoor fans within a single indoor unit, the number of indoor fans; the nominal cooling capacity of the indoor unit and outdoor unit; which fan(s) operate to attain the full-load air volume rate when controls limit the simultaneous operation of all fans within the single indoor unit; and the allocation of the full-load air volume rate to each operational fan when different capacity blowers are connected to the common duct;
(iv) For blower coil systems, the airflow-control settings associated with full load cooling operation; and the airflow-control settings or alternative instructions for setting fan speed to the speed upon which the rating is based;
(v) For models with time-adaptive defrost control, the frosting interval to be used during Frost Accumulation tests and the procedure for manually initiating the defrost at the specified time;
(vi) For models of indoor units designed for both horizontal and vertical installation or for both up-flow and down-flow vertical installations, the orientation used for testing;
(vii) For variable-speed models, the compressor frequency set points, and the required dip switch/control settings for step or variable components;
(viii) For variable-speed heat pumps, whether the H1N or H12 test speed is the same as the H32 test speed; the compressor frequency that corresponds to maximum speed at which the system controls would operate the compressor in normal operation in a 17 °F ambient temperature; and when certifying compliance with January 1, 2023, energy conservation standards, whether the optional 5 °F very low temperature heating mode test was used to characterize performance at temperatures below 17 °F (except for triple-capacity northern heat pumps, for which the very low temperature test is required,) and whether the alternative test required for minimum-speed-limiting variable-speed heat pumps was used;
(ix) For models of outdoor units with no match, the following characteristics of the indoor coil: The face area, the coil depth in the direction of airflow, the fin density (fins per inch), the fin material, the fin style, the tube diameter, the tube material, and the numbers of tubes high and deep; and
(x) For central air conditioners and heat pumps that have two-capacity compressors that lock out low capacity operation for cooling at higher outdoor temperatures and/or heating at lower outdoor temperatures, the outdoor temperature(s) at which the unit locks out low capacity operation.
(f)Represented values for the Federal Trade Commission. Use the following represented value determinations to meet the requirements of the Federal Trade Commission.
(1)Annual Operating Cost-Cooling. Determine the represented value of estimated annual operating cost for cooling-only units or the cooling portion of the estimated annual operating cost for air-source heat pumps that provide both heating and cooling by calculating the product of:
(i) The value determined in paragraph (f)(1)(i)(A) of this section if using appendix M to subpart B of part 430 or the value determined in paragraph (f)(1)(i)(B) of this section if using appendix M1 to subpart B of part 430;
(A) The quotient of the represented value of cooling capacity, in Btu's per hour as determined in paragraph (b)(3)(iii) of this section, divided by the represented value of SEER, in Btu's per watt-hour, as determined in paragraph (b)(3)(ii) of this section;
(B) The quotient of the represented value of cooling capacity, in Btu's per hour as determined in paragraph (b)(3)(iii) of this section, and multiplied by 0.93 for variable-speed heat pumps only, divided by the represented value of SEER2, in Btu's per watt-hour, as determined in paragraph (b)(3)(ii) of this section.
(ii) The representative average use cycle for cooling of 1,000 hours per year;
(iii) A conversion factor of 0.001 kilowatt per watt; and
(iv) The representative average unit cost of electricity in dollars per kilowatt-hour as provided pursuant to section 323(b)(2) of the Act.
(2)Annual Operating Cost-Heating. Determine the represented value of estimated annual operating cost for air-source heat pumps that provide only heating or for the heating portion of the estimated annual operating cost for air-source heat pumps that provide both heating and cooling, as follows:
(i) When using appendix M to subpart B of part 430, the product of:
(A) The quotient of the mean of the standardized design heating requirement for the sample, in Btu's per hour, nearest to the Region IV minimum design heating requirement, determined for each unit in the sample in section 4.2 of appendix M to subpart B of part 430, divided by the represented value of heating seasonal performance factor (HSPF), in Btu's per watt-hour, calculated for Region IV corresponding to the above-mentioned standardized design heating requirement, as determined in paragraph (b)(3)(ii) of this section;
(B) The representative average use cycle for heating of 2,080 hours per year;
(C) The adjustment factor of 0.77, which serves to adjust the calculated design heating requirement and heating load hours to the actual load experienced by a heating system;
(D) A conversion factor of 0.001 kilowatt per watt; and
(E) The representative average unit cost of electricity in dollars per kilowatt-hour as provided pursuant to section 323(b)(2) of the Act;
(ii) When using appendix M1 to subpart B of part 430, the product of:
(A) The quotient of the represented value of cooling capacity (for air-source heat pumps that provide both cooling and heating) in Btu's per hour, as determined in paragraph (b)(3)(iii) of this section, or the represented value of heating capacity (for air-source heat pumps that provide only heating), as determined in paragraph (b)(3)(i)(D) of this section, divided by the represented value of heating seasonal performance factor 2 (HSPF2), in Btu's per watt-hour, calculated for Region IV, as determined in paragraph (b)(3)(ii) of this section;
(B) The representative average use cycle for heating of 1,572 hours per year;
(C) The adjustment factor of 1.15 (for heat pumps that are not variable-speed) or 1.07 (for heat pumps that are variable-speed), which serves to adjust the calculated design heating requirement and heating load hours to the actual load experienced by a heating system;
(D) A conversion factor of 0.001 kilowatt per watt; and
(E) The representative average unit cost of electricity in dollars per kilowatt-hour as provided pursuant to section 323(b)(2) of the Act;
(3)Annual Operating Cost-Total. Determine the represented value of estimated annual operating cost for air-source heat pumps that provide both heating and cooling by calculating the sum of the quantity determined in paragraph (f)(1) of this section added to the quantity determined in paragraph (f)(2) of this section.
(4)Regional Annual Operating Cost-Cooling. Determine the represented value of estimated regional annual operating cost for cooling-only units or the cooling portion of the estimated regional annual operating cost for air-source heat pumps that provide both heating and cooling by calculating the product of:
(i) The value determined in paragraph (f)(4)(i)(A) of this section if using appendix M to subpart B of part 430 or the value determined in paragraph (f)(4)(i)(B) of this section if using appendix M1 to subpart B of part 430;
(A) The quotient of the represented value of cooling capacity, in Btu's per hour as determined in paragraph (b)(3)(iii) of this section, divided by the represented value of SEER, in Btu's per watt-hour, as determined in paragraph (b)(3)(ii) of this section;
(B) The quotient of the represented value of cooling capacity, in Btu's per hour as determined in paragraph (b)(3)(iii) of this section, and multiplied by 0.93 for variable-speed heat pumps only, divided by the represented value of SEER2, in Btu's per watt-hour, as determined in paragraph (b)(3)(ii) of this section;
(ii) The value determined in paragraph (f)(4)(ii)(A) of this section if using appendix M to subpart B of part 430 or the value determined in paragraph (f)(4)(ii)(B) of this section if using appendix M1 to subpart B of part 430;
(A) The estimated number of regional cooling load hours per year determined from Table 22 in section 4.4 of appendix M to subpart B of part 430;
(B) The estimated number of regional cooling load hours per year determined from Table 21 in section 4.4 of appendix M1 to subpart B of part 430;
(iii) A conversion factor of 0.001 kilowatts per watt; and
(iv) The representative average unit cost of electricity in dollars per kilowatt-hour as provided pursuant to section 323(b)(2) of the Act.
(5)Regional Annual Operating Cost-Heating. Determine the represented value of estimated regional annual operating cost for air-source heat pumps that provide only heating or for the heating portion of the estimated regional annual operating cost for air-source heat pumps that provide both heating and cooling as follows:
(i) When using appendix M to subpart B of part 430, the product of:
(A) The estimated number of regional heating load hours per year determined from Table 22 in section 4.4 of appendix M to subpart B of part 430;
(B) The quotient of the mean of the standardized design heating requirement for the sample, in Btu's per hour, for the appropriate generalized climatic region of interest (i.e., corresponding to the regional heating load hours from "A") and determined for each unit in the sample in section 4.2 of appendix M to subpart B of part 430, divided by the represented value of HSPF, in Btu's per watt-hour, calculated for the appropriate generalized climatic region of interest and corresponding to the above-mentioned standardized design heating requirement, and determined in paragraph (b)(3)(ii);
(C) The adjustment factor of 0.77; which serves to adjust the calculated design heating requirement and heating load hours to the actual load experienced by a heating system;
(D) A conversion factor of 0.001 kilowatts per watt; and
(E) The representative average unit cost of electricity in dollars per kilowatt-hour as provided pursuant to section 323(b)(2) of the Act.
(ii) When using appendix M1 to subpart B of part 430, the product of:
(A) The estimated number of regional heating load hours per year determined from Table 21 in section 4.4 of appendix M1 to subpart B of part 430;
(B) The quotient of the represented value of cooling capacity (for air-source heat pumps that provide both cooling and heating) in Btu's per hour, as determined in paragraph (b)(3)(i)(C) of this section, or the represented value of heating capacity (for air-source heat pumps that provide only heating), as determined in paragraph (b)(3)(i)(D) of this section, divided by the represented value of HSPF2, in Btu's per watt-hour, calculated for the appropriate generalized climatic region of interest, and determined in paragraph (b)(3)(i)(B) of this section;
(C) The adjustment factor of 1.15 (for heat pumps that are not variable-speed) or 1.07 (for heat pumps that are variable-speed), which serves to adjust the calculated design heating requirement and heating load hours to the actual load experienced by a heating system;
(D) A conversion factor of 0.001 kilowatts per watt; and
(E) The representative average unit cost of electricity in dollars per kilowatt-hour as provided pursuant to section 323(b)(2) of the Act.
(6)Regional Annual Operating Cost-Total. For air-source heat pumps that provide both heating and cooling, the estimated regional annual operating cost is the sum of the quantity determined in paragraph (f)(4) of this section added to the quantity determined in paragraph (f)(5) of this section.
(7)Annual Operating Cost-Rounding. Round any represented values of estimated annual operating cost determined in paragraphs (f)(1) through (6) of this section to the nearest dollar per year.

10 C.F.R. §429.16

81 FR 37049 , June 8, 2016, as amended at 81 FR 55112 , Aug. 18, 2016; 82 FR 1468 , Jan. 5, 2017; 86 FR 68393 , Dec. 2, 2021; 87 FR 64583 , Oct. 25, 2022
81 FR 37049, 7/8/2016; as amended by T.D. 9782, 81 FR 55112, 8/18/2016; 82 FR 1468, 2/6/2017; 82 FR 32227, 7/13/2017; 83 FR 39873, 8/13/2018; 86 FR 68393, 12/2/2021; 87 FR 64586, 11/25/2022