Table 5 - Hydrostatic Test Interval for Extinguishers

Extinguisher typeTest Interval (Years)
Stored Pressure Water and/or Antifreeze/Loaded Stream5
AFFF (Aqueous Film Forming Foam)5
FFFP (Film Forming Fluoroprotein Foam)5
Wet Chemical5
Dry Chemical with Stainless Steel Shells5
Carbon Dioxide5
Dry Chemical, Stored Pressure with Mild Steel Shells, Brazed Brass Shells, or Aluminum Shells12
Dry Chemical, Cartridge and Cylinder-Operated, with Mild Steel Shells12
Halogenated Agents12
Dry Powder, stored pressure, cartridge- or cylinder-operated with mild steel shells12