Table 5
Hydrostatic Test Interval for Extinguishers
Extinguisher type | Test Interval (Years) |
Stored Pressure Water | 5 |
and/or Antifreeze/Loaded Stream | |
AFFF (Aqueous Film Forming Foam) | 5 |
FFFP (Film Forming Fluoroprotein Foam) | 5 |
Wet Chemical | 5 |
Dry Chemical with Stainless Steel Shells | 5 |
Carbon Dioxide | 5 |
Dry Chemical, Stored Pressure with | |
Mild Steel Shells, Brazed Brass | |
Shells, or Aluminum Shells | 12 |
Dry Chemical, Cartridge and Cylinder-Operated, | |
with Mild Steel Shells | 12 |
Halogenated Agents | 12 |
Dry Powder, stored pressure, cartridge- or cylinder-operated | |
with mild steel shells | 12 |