Table 1. Emission Standards for New Stationary Emergency Standby Diesel-Fueled CI Engines g/bhp-hr (g/kW-hr)
Maximum Engine Power | Model year(s) | PM | NMHC+NOx | CO |
50 [LESS THAN EQUAL TO] HP < 75 | 2007 | 0.15 (0.20) | 5.6 (7.5) | 3.7 (5.0) |
(37 [LESS THAN EQUAL TO] kW < 56) | 2008+ | 3.5 (4.7) | ||
75 [LESS THAN EQUAL TO] HP < 100 | 2007 | 0.15 (0.20) | 5.6 (7.5) | 3.7 (5.0) |
(56 [LESS THAN EQUAL TO] kW < 75) | 2008+ | 3.5 (4.7) | ||
100 [LESS THAN EQUAL TO] HP < 175 | 2007 | 0.15 (0.20) | 3.0 (4.0) | 3.7 (5.0) |
(75 [LESS THAN EQUAL TO] kW < 130) | 2008+ | |||
175 [LESS THAN EQUAL TO] HP < 300 | 2007 | 0.15 (0.20) | 3.0 (4.0) | 2.6 (3.5) |
(130 [LESS THAN EQUAL TO] kW < 225) | 2008+ | |||
300 [LESS THAN EQUAL TO] HP < 600 | 2007 | 0.15 (0.20) | 3.0 (4.0) | 2.6 (3.5) |
(225 [LESS THAN EQUAL TO] kW < 450) | 2008+ | |||
600 [LESS THAN EQUAL TO] HP < 750 | 2007 | 0.15 (0.20) | 3.0 (4.0) | 2.6 (3.5) |
(450 [LESS THAN EQUAL TO] kW < 560) | 2008+ | |||
HP > 750 | 2007 | 0.15 (0.20) | 4.8 (6.4) | 2.6 (3.5) |
(kW > 560) | 2008+ | |||
__________ | ||||
1. May be subject to additional emission limitations as specified in current applicable district rules, regulations or policies. |
Table 2. Emission Standards for New Stationary Emergency Standby Direct-Drive Fire Pump Engines > 50 BHP g/bhp-hr (g/kW-hr)
Maximum Engine Power | Model year(s) | PM | NMHC+NOx | CO |
50 [LESS THAN EQUAL TO] HP < 75 | 2010 and earlier | 0.60 (0.80) | 7.8 (10.5) | 3.7 (5.0) |
(37 [LESS THAN EQUAL TO] kW < 56) | 2011+1 | 0.30 (0.40) | 3.5 (4.7) | |
75 [LESS THAN EQUAL TO] HP < 100 | 2010 and earlier | 0.60 (0.80) | 7.8 (10.5) | 3.7 (5.0) |
(56 [LESS THAN EQUAL TO] kW < 75) | 2011+1 | 0.30 (0.40) | 3.5 (4.7) | |
100 [LESS THAN EQUAL TO] HP < 175 | 2009 and earlier | 0.60 (0.80) | 7.8 (10.5) | 3.7 (5.0) |
(75 [LESS THAN EQUAL TO] kW < 130) | 2010+2 | 0.22 (0.30) | 3.0 (4.0) | |
175 [LESS THAN EQUAL TO] HP < 300 | 2008 and earlier | 0.40 (0.54) | 7.8 (10.5) | 2.6 (3.5) |
(130 [LESS THAN EQUAL TO] kW < 225) | 2009+3 | 0.15 (0.20) | 3.0 (4.0) | |
300 [LESS THAN EQUAL TO] HP < 600 | 2008 and earlier | 0.40 (0.54) | 7.8 (10.5) | 2.6 (3.5) |
(225 [LESS THAN EQUAL TO] kW < 450) | 2009+3 | 0.15 (0.20) | 3.0 (4.0) | |
600 [LESS THAN EQUAL TO] HP < 750 | 2008 and earlier | 0.40 (0.54) | 7.8 (10.5) | 2.6 (3.5) |
(450 [LESS THAN EQUAL TO] kW < 560) | 2009+ | 0.15 (0.20) | 3.0 (4.0) | |
HP > 750 | 2007 and earlier | 0.40 (0.54) | 7.8 (10.5) | 2.6 (3.5) |
(kW > 560) | 2008+ | 0.15 (0.20) | 4.8 (6.4) | |
__________ | ||||
1. For model years 2011-2013, manufacturers, owners and operators of fire pump stationary CI ICE in this engine power category with a rated speed of greater than 2,650 revolutions per minute (rpm) may comply with the emission limitations for 2010 model year engines. | ||||
2. For model years 2010-2012, manufacturers, owners and operators of fire pump stationary CI ICE in this engine power category with a rated speed of greater than 2,650 rpm may comply with the emission limitations for 2009 model year engines. | ||||
3. In model years 2009-2011, manufacturers of fire pump stationary CI ICE in this engine power category with a rated speed of greater than 2,650 rpm may comply with the emission limitations for 2008 model year engines. |
Table 3. Summary of the Emission Standards and Operating Requirements for In-Use Stationary Emergency Standby Diesel-Fueled CI Engines > 50 BHP (See section 93115.6(a)(3))
Maximum Engine Power | Model year(s) | PM | NMHC+NOx | CO |
50 [LESS THAN EQUAL TO] HP < 75 | 2010 and earlier | 0.60 (0.80) | 7.8 (10.5) | 3.7 (5.0) |
(37 [LESS THAN EQUAL TO] kW < 56) | 2011+1 | 0.30 (0.40) | 3.5 (4.7) | |
75 [LESS THAN EQUAL TO] HP < 100 | 2010 and earlier | 0.60 (0.80) | 7.8 (10.5) | 3.7 (5.0) |
(56 [LESS THAN EQUAL TO] kW < 75) | 2011+1 | 0.30 (0.40) | 3.5 (4.7) | |
100 [LESS THAN EQUAL TO] HP < 175 | 2009 and earlier | 0.60 (0.80) | 7.8 (10.5) | 3.7 (5.0) |
(75 [LESS THAN EQUAL TO] kW < 130) | 2010+2 | 0.22 (0.30) | 3.0 (4.0) | |
175 [LESS THAN EQUAL TO] HP < 300 | 2008 and earlier | 0.40 (0.54) | 7.8 (10.5) | 2.6 (3.5) |
(130 [LESS THAN EQUAL TO] kW < 225) | 2009+3 | 0.15 (0.20) | 3.0 (4.0) | |
300 [LESS THAN EQUAL TO] HP < 600 | 2008 and earlier | 0.40 (0.54) | 7.8 (10.5) | 2.6 (3.5) |
(225 [LESS THAN EQUAL TO] kW < 450) | 2009+3 | 0.15 (0.20) | 3.0 (4.0) | |
600 [LESS THAN EQUAL TO] HP < 750 | 2008 and earlier | 0.40 (0.54) | 7.8 (10.5) | 2.6 (3.5) |
(450 [LESS THAN EQUAL TO] kW < 560) | 2009+ | 0.15 (0.20) | 3.0 (4.0) | |
HP > 750 | 2007 and earlier | 0.40 (0.54) | 7.8 (10.5) | 2.6 (3.5) |
(kW > 560) | 2008+ | 0.15 (0.20) | 4.8 (6.4) | |
__________ | ||||
1. For model years 2011-2013, manufacturers, owners and operators of fire pump stationary CI ICE in this engine power category with a rated speed of greater than 2,650 revolutions per minute (rpm) may comply with the emission limitations for 2010 model year engines. | ||||
2. For model years 2010-2012, manufacturers, owners and operators of fire pump stationary CI ICE in this engine power category with a rated speed of greater than 2,650 rpm may comply with the emission limitations for 2009 model year engines. | ||||
3. In model years 2009-2011, manufacturers of fire pump stationary CI ICE in this engine power category with a rated speed of greater than 2,650 rpm may comply with the emission limitations for 2008 model year engines. |
Owners or operators that choose to meet the diesel PM standards defined in section 93115.6(b)(3)(A) with emission control strategies that are not verified through the Verification Procedure shall either:
Not increase HC or NOx emission rates by more than 10% above baseline; or
Not increase the sum of NMHC and NOx emission rates above baseline.
Owners or operators that choose to meet the diesel PM standards and hour of operation limits defined in section 93115.6(c)(2)(C) with emission control strategies that are not verified through the Verification Procedure shall either:
After a DRP is terminated by either the Utility Distribution Company or the engine owner or operator, the DRP engine shall remain subject to the requirements of section 93115.6(c) as if the DRP were still in effect.
Cal. Code Regs. Tit. 17, § 93115.6
2. Editorial correction of subsection (c)(2)(B) (Register 2008, No. 17).
3. Change without regulatory effect redesignating subsections (c)(2)(B)a.-e. as subsections (c)(2)(B)1.-5. filed 4-21-2008 pursuant to section 100, title 1, California Code of Regulations (Register 2008, No. 17).
4. Amendment filed 5-19-2011; operative 5-19-2011 pursuant to Government Code section 11343.4 (Register 2011, No. 20).
Note: Authority cited: Sections 39600, 39601, 39658, 39659, 39666, 41511 and 43013, Health and Safety Code. Reference: Sections 39002, 39650, 39658, 39659, 39666, 40000, 41511 and 43013, Health and Safety Code.
2. Editorial correction of subsection (c)(2)(B) (Register 2008, No. 17).
3. Change without regulatory effect redesignating subsections (c)(2)(B)a.-e. as subsections (c)(2)(B)1.-5. filed 4-21-2008 pursuant to section 100, title 1, California Code of Regulations (Register 2008, No. 17).
4. Amendment filed 5-19-2011; operative 5-19-2011 pursuant to Government Code section 11343.4 (Register 2011, No. 20).