If the HVAC system does not meet the minimum ventilation rate requirements, the certified energy auditor or qualified adjusting personnel shall review the HVAC system airflow and capacity to determine if additional ventilation can be provided without adversely impacting equipment performance and building indoor environmental quality. If additional ventilation can be provided, qualified adjusting personnel shall adjust ventilation rates to meet the minimum ventilation rate requirements set forth, pursuant to this paragraph, to the extent feasible. After the adjustment, the measurement of outside air and verification of whether the HVAC system provides the minimum outside air ventilation rates calculated under this subparagraph shall be repeated. If minimum ventilation rate requirements cannot be met, this deficiency shall be reported in the assessment report and the verification report and shall be addressed by a certified energy auditor, as required;
N.J.S. § 48:3-106.4