053-4 Wyo. Code R. § 75.601-3

Current through April 27, 2019
Section 75.601-3 - Short circuit protection; dual element fuses; current ratings; maximum values

Dual element fuses having adequate current-interrupting capacity shall meet the requirements for short circuit protection of trailing cables as provided in S 75.601, however, the current ratings of such devices shall not exceed the maximum values specified in this section:

Conductor size (AWG or MGM)

Single conductor cable Ampacity Max. fuse rating

Two conductor cable Ampacity Max. fuse rating

14

15

15

12

20

20

10

25

25

8

60

60

50

50

6

85

90

65

70

4

110

110

90

90

3

130

150

105

110

2

150

150

120

125

1

170

175

140

150

1/0

200

200

170

175

2/0

235

250

195

200

3/0

275

300

225

225

4/0

315

350

260

300

250

350

350

285

300

300

395

400

310

350

350

445

450

335

350

400

480

500

360

400

450

515

600

385

400

500

545

600

415

450

053-4 Wyo. Code R. § 75.601-3