Section 75.601-1 - Short circuit protection; rating and setting of circuit breakers

Circuit breakers providing short circuit protection for trailing cables shall be set so as not to exceed the maximum allowable instantaneous settings specified in this section; however, higher settings may be permitted by an authorized representative of the Secretary when he has determined that special applications are justified:

Conductor size AWG or MGM

Maximum allowable circuit breaker instantaneous setting (amperes)

14

50

12

75

10

150

8

200

6

300

4

500

3

600

2

800

1

1,000

1/0

1,250

2/0

1,500

3/0

2,000

4/0

2,500

250

2,500

300

2,500

350

2,500

400

2,500

450

2,500

500

2,500