(a) Firefighting equipment shall be inspected according to the following schedules:
(b) At the completion of each inspection or test required by this standard, the person making the inspection or test shall certify that the inspection or test has been made and the date on which it was made. Certifications of hydrostatic testing shall be retained until the fire extinguisher is retested or permanently removed from service. Other certifications shall be retained for one year.
Table C-1-Hydrostatic Test Intervals for Fire Extinguishers
Extinguisher type | Test interval (years) |
Soda Acid | 5 |
Cartridge-Operated Water and/or Antifreeze | 5 |
Stored-Pressure Water and/or Antifreeze | 5 |
Wetting Agent | 5 |
Foam | 5 |
AFFF (Aqueous Film Forming Foam) | 5 |
Loaded Stream | 5 |
Dry-Chemical with Stainless Steel Shells | 5 |
Carbon Dioxide | 5 |
Dry-Chemical, Stored Pressure, with Mild Steel Shells, Brazed Brass Shells, or Aluminum Shells | 12 |
Dry-Chemical, Cartridge or Cylinder Operated, with Mild Steel Shells | 12 |
Bromotrifluoromethane-Halon 1301 | 12 |
Bromochlorodifluoromethane-Halon 1211 | 12 |
Dry-Powder, Cartridge or Cylinder-Operated, with Mild Steel Shells/1 | 12 |
1/Except for stainless steel and steel used for compressed gas cylinders, all other steel shells are defined as "mild steel" shells.
053-2 Wyo. Code R. § 56.4201