045-11 Wyo. Code R. § 11-4

Current through April 27, 2019
Section 11-4 - Specific Provisions-Distribution Lines

(a) Pertinent portions of Section 3 apply to this section as well.

(b) Service connection crossings to customers shall be held to a minimum by installing major feeder lines across the highway R/W and starting distribution on the other side of the highway.

(c) Hydrants, meter boxes and service line shut off valves shall be located off the highway R/ W whenever possible.

(d) Service connections to customers and lines to hydrants shall, at a minimum, be constructed below frost line but not less than four (4) feet below the top of the roadway or adjacent natural ground.

045-11 Wyo. Code R. § 11-4