020-1 Wyo. Code R. § 1-15

Current through April 27, 2019
Section 1-15 - Petroleum USTs with a Capacity of 2,000 Gallons or Less

Tanks installed on or after December 1, 2005, shall be double-wall systems and interstitially monitored. Tanks installed on or before November 30, 2005, shall be monitored for releases at least every 30 days using one of the methods listed in Section 16. Tanks with a capacity of 550 gallons or less and tanks with a capacity of 551 to 1,000 gallons that meet the tank diameter criteria in Table 1 may use manual tank gauging as the sole method of release detection in accordance with Section 15(a). All other tanks with a nominal capacity of 551 to 2,000 gallons may use manual tank gauging in place of inventory control.

(a) Manual Tank Gauging. Manual tank gauging shall meet the following requirements:

  • (i) Tank liquid level measurements shall be taken at the beginning and ending of the minimum test duration shown in Table 1 during which no liquid is added to or removed from the tank;
  • (ii) Level measurements shall be based on an average of two consecutive stick readings at both the beginning and end of the period;
  • (iii) The equipment used shall be capable of measuring the depth of the regulated substance over the full range of the UST's height to the nearest one-eighth of an inch;
  • (iv) A suspected release shall be declared and the requirements of Part E shall be followed if the variation between beginning and ending measurements exceeds the weekly or monthly standards in Table 1:

    TABLE 1 MANUAL TANK GAUGING VARIATION STANDARDS
    Nominal Tank Capacity Weekly Standard (one test) Monthly Standard (average of four tests) Minimum Test Duration Hours*
    550 gallons or less 10 gallons 5 gallons 36
    551-1,000 gallons (when the tank diameter is 64") 9 gallons 4 gallons 44
    551-1,000 gallons (when the tank diameter is 48") 12 gallons 6 gallons 58
    551-1,000 gallons 13 gallons 7 gallons 36
    1,001-2,000 gallons 26 gallons 13 gallons 36

    * Nothing can be added to or removed from the UST for the duration of the test.

(b) Other Release Detection Methods. Owners and/or operators of petroleum USTs with a capacity of 2,000 gallons or less may also use any of the release detection methods listed in Section 16(a) through (j).

020-1 Wyo. Code R. § 1-15

Adopted, Eff. 6/29/2018.