020-17 Wyo. Code R. § 17-30

Current through April 27, 2019
Section 17-30 - Temporary Closure

(a) General Requirements. When an storage tank system is temporarily closed, owners and/or operators shall continue operation and maintenance of CP systems in accordance with Section 11. Owners and/or operators shall continue release detection in accordance with Part D as long as the tank contains more than one inch of regulated substance at the measuring point directly under the fill tube. Parts E and F shall be complied with if a release is suspected or confirmed.

(b) Six (6) months or more. When a storage tank system is temporarily closed for six (6) months or more, owners and/or operators shall also comply with the following requirements:

  • (i) Leave vent piping open and functioning; and
  • (ii) Drain, cap and secure all other connected piping, pumps, manways, and ancillary equipment; and
  • (iii) Continue to pay the annual tank fee and maintain financial responsibility pursuant to Chapter 19, Wyoming Water Quality Rules and Regulations, Financial Responsibility for USTs.

(c) Three (3) years or more. When a storage tank system is temporarily closed for more than three (3) years, the owner and/or operator shall complete a minimum site assessment in accordance with Section 29.

020-17 Wyo. Code R. § 17-30