(a) Test procedures. Test procedures for analysis of monitoring samples shall conform to regulations published pursuant to Section 304(g) of the Federal Water Pollution Control Act ( 33 U.S.C. 466 et. seq.).
(b) Testing requirements. All treatment plants shall have capability to perform or contract for the self-monitoring analytical work required by discharge permits or ground water monitoring requirements. All plants shall in addition be capable of performing or contracting out the analytical work required to ensure good management and control of plant operation and performance. Plants operating under requirements of an industrial pretreatment program must have the capability of performing or must contract out the necessary testing to maintain the program as approved by the reviewing agency.
(c) Minimum requirements. A minimum of 400 square feet (37.2 m2) of floor space shall be provided for the laboratory where an analysis program for a fulltime laboratory chemist is proposed. If more than two persons will be working in the laboratory, 100 square feet (9.3 m2) of additional space shall be provided for each additional person. Bench top height shall be thirty-six (36) inches (0.91 m). Tops should be field joined into a continuous surface with acid, alkali, and solvent-resistant cements.
(d) Portable testing equipment. Portable testing equipment shall be provided where necessary for operational control testing or industrial waste testing. Portable testing may be used for testing as necessary, provided the testing procedure meets the requirements of Section 304(g) of the Federal Water Pollution Control Act, if the results are to be used for permit reporting. Non-EPA certified procedures may be used for operational control or gross data generation.
020-11 Wyo. Code R. § 11-23
Amended, Eff. 6/29/2018.