010-4 Wyo. Code R. § 4-18

Current through April 27, 2019
Section 4-18 - Spa Outlets

(a) A spa outlet shall be designed so that the pumping system complies with one of the following:

  • (i) Two (2) outlets of equal pipe diameter size designed so that:
    • (A) Neither one of the two outlets be cut out of the suction line by a valve; or
    • (B) By other means which would prevent entrapment of the bather on the suction orifices.
  • (ii) One antivortex drain:
    • (A) The antivortex drain shall not present a tripping or stubbing hazard to the feet; and
    • (B) The diameter of the antivortex plate shall be at least six (6) inches (15cm).
  • (iii) An open area of one-hundred forty-four (144) square inches (928 cm²) or larger grate.

(b) All outlet grates, antivortex plates and inlet fittings shall have tamper-proof screws; and

  • (i) Grates, vortex plates and inlet fittings shall be in place whenever the spa is in use.

010-4 Wyo. Code R. § 4-18