Current through November 25, 2024
Section NR 811.83 - Emergency power requirementsBoosted pressure zone emergency power installations shall meet the following requirements:
(1) Emergency power shall be provided if 50 or fewer living units are being served and the primary pressure zone cannot maintain positive pressures of 3 psi or greater at street elevation in all areas served by the booster pumps, and sufficient elevated storage is not provided.(2) Emergency power shall be provided if more than 50 living units are being served and the primary pressure zone cannot maintain pressures of 20 psi or greater at street elevation in all areas served by the booster pumps, and sufficient elevated storage is not provided.(3) Emergency power shall consist of a dedicated on-site engine-generator set with an automatic transfer switch capable of powering at minimum the domestic service pumps and station building demands.Wis. Admin. Code Department of Natural Resources NR 811.83
CR 09-073: cr. Register November 2010 No. 659, eff. 12-1-10.