Wis. Admin. Code Department of Natural Resources NR 667.0194

Current through August 26, 2024
Section NR 667.0194 - What installation requirements shall I follow?
(1) Support and protect ancillary equipment against physical damage and excessive stress due to settlement, vibration, expansion or contraction.
(2) Provide the type and degree of corrosion protection recommended by an independent corrosion expert, based on the information provided under s. NR 667.0191(3), to ensure the integrity of the tank system during use of the tank system. An independent corrosion expert shall supervise the installation of a corrosion protection system that is field fabricated to ensure proper installation.
(3) Obtain and keep at the facility written statements by those persons required to certify the design of the tank system and to supervise the installation of the tank system as required in subs. (1) and (2) and ss. NR 667.0192 and 667.0193. The written statement shall attest that the tank system was properly designed and installed and that you made repairs under ss. NR 667.0192 and 667.0193. These written statements shall also include the certification statement as required in s. NR 670.011(4).

Wis. Admin. Code Department of Natural Resources NR 667.0194

Adopted by, CR 16-007: cr. Register July 2017 No. 739, eff. 8-1-17; correction in (3) made under s. 35.17, Stats., Register July 2017 No. 739, eff.8/1/2017