Wis. Admin. Code Department of Natural Resources NR 664.0195

Current through November 25, 2024
Section NR 664.0195 - Inspections
(1) The owner or operator shall develop and follow a schedule and procedure for inspecting overfill controls.
(2) The owner or operator shall inspect at least once each operating day data gathered from monitoring and leak detection equipment (for example, pressure or temperature gauges, monitoring wells) to ensure that the tank system is being operated according to its design.

Note: Section NR 664.0015(3) requires the owner or operator to remedy any deterioration or malfunction found. Section NR 664.0196 requires the owner or operator to notify the department within 24 hours of confirming a leak. Also, if a hazardous substance is released to the environment, 40 CFR part 302 may require the owner or operator to notify the national response center and s. 292.11, Stats., and ch. NR 706 may require the owner or operator to notify the department.

(3) In addition, except as noted under sub. (4), the owner or operator shall inspect at least once each operating day:
(a) Above ground portions of the tank system, if any, to detect corrosion or releases of waste.
(b) The construction materials and the area immediately surrounding the externally accessible portion of the tank system, including the secondary containment system (for example, dikes) to detect erosion or signs of releases of hazardous waste (for example, wet spots, dead vegetation).
(4) Owners or operators of tank systems that either use leak detection systems to alert facility personnel to leaks, or implement established workplace practices to ensure leaks are promptly identified, shall inspect at least weekly those areas described in sub. (3) (a) and (b). Use of the alternate inspection schedule shall be documented in the facility's operating record. This documentation shall include a description of the established workplace practices at the facility.
(5) Ancillary equipment that is not provided with secondary containment, as described in s. NR 664.0193(6) (a) to (d), shall be inspected at least once each operating day.
(6) The owner or operator shall inspect cathodic protection systems, if present, according to, at a minimum, all of the following requirements to ensure that they are functioning properly:
(a) The proper operation of the cathodic protection system shall be confirmed within 6 months after initial installation and annually thereafter.
(b) All sources of impressed current shall be inspected or tested, or both, as appropriate, at least bimonthly (that is, every other month).

Note: The practices described in the National Association of Corrosion Engineers (NACE) standard, "Recommended Practice (RP-02-85)-Control of External Corrosion on Metallic Buried, Partially Buried, or Submerged Liquid Storage Systems" and the American Petroleum Institute (API) Publication 1632, "Cathodic Protection of Underground Petroleum Storage Tanks and Piping Systems", may be used, where applicable, as guidelines in maintaining and inspecting cathodic protection systems.

(7) The owner or operator shall document in the operating record of the facility an inspection of those items in subs. (1) to (3).

Wis. Admin. Code Department of Natural Resources NR 664.0195

CR 05-032: cr. Register July 2006 No. 607, eff. 8-1-06.
Amended by, CR 16-007: r. and recr. (2) to (4), cr. (5) to (7) Register July 2017 No. 739, eff.8/1/2017