Section NR 488.07 - Approval of refrigerant recovery equipment(1) The department may approve refrigerant recovery equipment if all of the following conditions are met:(a) A nationally recognized testing laboratory has approved the recovery equipment.(b) The department determines that the laboratory's approval is based on adequate testing for safety and recovery efficiency.(c) The refrigerant recovery equipment is capable of recovering at least 90% of refrigerant remaining in salvaged or dismantled refrigeration equipment.(2) Refrigerant recovery equipment approved by the department of agriculture, trade & consumer protection under ch. ATCP 136 or the department of safety and professional services under ch. SPS 345 is considered approved under this section.Wis. Admin. Code Department of Natural Resources NR 488.07